MOUNTING THE UNIT
1) The unit should be mounted as close to the point of use as possible.
2) This unit must only be mounted in the vertical position with the water fittings located at the
bottom of the unit. Mounting other than in the vertical position WILL cause element burn out.
3) The cold water inlet is on the right hand side and the hot water outlet is on the left hand side.
Under NO circumstances can these be reversed.
4) Leave a minimum of 8” above the unit for easy replacement of the elements.
5) The heater should be fixed to the wall using screws in the four mounting holes at each corner
of the backplate.
6) The unit should be installed in the plumbing system in such a way that there is no tendency
for the unit to be starved of water: for example: by an excessive draw-off of cold water just
before the unit. Also do not fit an unrestricted hot water draw-off point below the heater as
this will tend to empty the heater by siphoning.
NOTE
ALL MOUNTING AND PLUMBING MUST BE COMPLETE BEFORE YOU PROCEED
WITH ELECTRICAL HOOK-UP.
TEST THE INSTALLATION FOR LEAKS BEFORE CONNECTING THE
ELECTRICAL SUPPLY.
3