COMFORT Object
COMFORT object (1 bit size) is visible only when
"Thermostat control mode" parameter is selected
with the value HVAC MODE.
When a telegram "1" is received thermostat goes in
COMFORT mode (it applies for both heating and
cooling)
On receipt of a telegram "0", thermostat returns to
the mode set by HVAC MODE object.
COMFORT mode can be set also with timing: after a
time set by a parameter thermostat returns in the
previous mode.
KNX PARAMETER
SETTINGS
Comfort Object
Time limited
Time unlimited
Comfort Overwrite Time
1.. 255 (minutes)
Object ENABLE HEATING/COOLING
This object is present only in HVAC Mode automatic.
If enabled, it allows you to enable or disable the
heating or cooling mode.
Enable Object
Cooling / Heating
Allows you to select which mode you can enable /
disable
State after download
disabled/enabled
Stabilisce se dopo un download la modalità
selezionata nel parametro precedente è abilitata o
disabilitata.
Activation telegram
Telegram to enable Cooling / Heating mode.
Object LOCK HEAT/COOL
This object is present only in automatic mode. If
enabled, it allows you to lock the heating or cooling
mode in the current state.
Lock Telegram
telegram
Telegram to block the mode.
WINDOW CONTACT Object
This object, if enabled, has higher priority than
HVAC MODE, SETPOINT MODE, COMFORT objects.
When a telegram is received ("0" or "1") on the
communication
object
WINDOW
CONTACT
thermostat enters a power saving mode:
KNX PARAMETER
SETTINGS
Action to execute for
setpoint
Modify Relative
Modify Absolute
Modify Relative
2 bytes Setpoint objects
for mode
2 bytes Setpoint objects
for adjustment
Upon receipt of a new
setpoint on this object,
the user adjustment is
recalculated,
always
taking into account the
limits
set
in
the
thermostat.
If set in transmission,
these objects send their
actual value every time it
changes
In this object we can find
the current value of the
user adjustment set in the
thermostat.
In the event that we want
to
reset
the
user's
override, simply send 0 on
that object.
If set in transmission, the
object will notify any
related user adjustment
on the bus
Modify absolute
2 bytes Setpoint objects
for mode
2 bytes Setpoint objects
for adjustment
Upon receipt of a new
setpoint on this object,
the thermostat considers
it as a new base setpoint
(warining, this means that
the temperature limits
that can be set in the
thermostat
are
recalculated), and the user
adjustment is reset
In this mode, the User
Adjustment object is used
to send a new current
setpoint (absolute value)
of the current mode to
the thermostat, always
taking into account the
limits
set
in
the
thermostat
with
the
parameter
allowed
In transmission this object
will not send anything on
the bus