Edwards SIGA-OSD Installation Sheet Download Page 1

 

 
© 2019 United Technologies Corporation 

1 / 2 

P/N 3102595-

EN • REV 001 • ISS 07MAR19 

 

 

SIGA-OSD Intelligent Optical 
Smoke Detector Installation 
Sheet 

 

 

Description 

The Signature Series model SIGA-OSD Intelligent Optical Smoke 
Detector is an intelligent device that uses an advanced optical sensing 
chamber to detect smoke. The detector analyzes data from the 
sensing chamber to recognize smoke from a fire while ignoring 
nuisance non-fire sources and whether to initiate an alarm to the Fire 
Alarm Control Panel. 

LED indicator. 

The LED indicator (see Figure 1 below) displays the 

following states: 

• 

Normal: Green LED indicator flashes, no action. 

• 

Alarm/active: Red LED indicator flashes, evacuate the area. 

Figure 1: SIGA-OSD features 

 

(1)  Self-locking tab 
(2)  LED indicator 

Installation  

Notes

 

• 

This detector does not operate without electrical power. As fires 
frequently cause power interruption, discuss further safeguards 
with the local fire protection specialist. 

• 

This detector does not sense fires in areas where smoke cannot 
reach the detector. Smoke from fires in walls, roofs, or on the 
opposite side of closed doors may not reach the detector. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to room 
temperature before applying power. 

• 

The dust cover (supplied) must remain on the detector during 
installation and be removed prior to commissioning and service. 
The dust cover is not a substitute for removing the detector during 
new construction or heavy remodeling. 

• 

Do not use smoke detectors with detector guards unless the 
combination has been evaluated and found suitable. 

• 

In Canada, install according to CAN/ULC-S524 

Standard for the 

Installation of Fire Alarm Systems,

 CSA

 

C22.1 

Canadian Electrical 

Code

, and the local authority having jurisdiction. 

• 

Upon completion of the original installation and following any 
modifications or additions to the system, perform a calibrated 
sensitivity test per NFPA code. The Signature Series devices can 
perform this test and the panel can generate a system sensitivity 
report. 

To install the detector: 

1. 

Install and wire the base, as described on the installation sheet 
supplied with the base. 

2. 

Remove the serial number label from the detector and attach it to 
the project documentation. 

3. 

Attach the detector to the base by rotating the detector clockwise 
until it snaps into the locked position. 

Testing 

Before testing, notify the proper authorities that the fire alarm system is 
undergoing maintenance and will be temporarily out of service. 

To perform an initial installation test: 

1.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

2.  For SIGA-OSD detectors placed in the air ducts, verify that the 

airflow is within specifications. See 

“Specifications” on page 2. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC circuit to verify 

operation of ground fault detection circuitry. 

5.  Run a system detector sensitivity report on all detectors and verify 

that the readings fall within acceptable limits. 

6.  Perform a sensor function test, as described below. 

To perform a sensor function test: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2