Edwards SIGA-270 Manual Download Page 1

Page 1 of 4

 

  D A T A   S H E E T

 E85001-0279

 

Not to be used for installation purposes.

  Issue 1  

EDWARDS

®

 Catalog 

u

 Intelligent Initiating

12-18-17

L I F E   S A F E T Y  

&  

I N C I D E N T   M A N A G E M E N T

SIGA-278

Overview

The SIGA-270 and SIGA-278 series Manual Pull Stations are part 
of EDWARDS’s Signature Series system. The SIGA-270 Fire Alarm 
Manual Pull Stations feature our very familiar teardrop shape. They 
are made from die-cast zinc and finished with red epoxy powder-
coat paint complemented by aluminum colored stripes and mark-
ings.  With positive pull-lever operation, one pull on the station 
handle breaks the glass rod and turns in a positive alarm, ensuring 
protection plus fool-proof operation. Presignal models (SIGA-270P) 
are equipped with a general alarm (GA) keyswitch for applications 
where two stage operation is required. The up-front highly visible 
glass rod discourages tampering, but is not required for proper 
operation.

EDWARDS’s double action single stage SIGA-278 station is a 
contemporary style manual station made from durable red colored 
lexan.  To initiate an alarm, first lift the upper door marked “LIFT 
THEN PULL HANDLE”, then pull the alarm handle.

Standard Features

Note: 

Some features described here may not be supported by all control sys-

tems. Check your control panel’s Installation and Operation Guide for details.

•  Traditional familiar appearance

 

 

SIGA-270 models feature our familiar teardrop design with 
simple positive pull action and sturdy die-cast metal body.

•  One stage (GA), two stage (pre-signal), and double action 

models

 

SIGA-270 models are available for one or two stage alarm 
systems. The single stage double action SIGA-278 features a 
rugged Lexan housing with keyed reset mechanism.

•  Break glass operation

 

An up-front visible glass rod on the SIGA-270 discourages 
tampering.

•  Intelligent device with integral microprocessor

 

All decisions are made at the station allowing lower com-
munication speed while substantially improving control panel 
response time. Less sensitive to line noise and loop wiring 
properties; twisted or shielded wire is not required.

•  ADA Compliant 

Meets ADA requirements for manual pull stations.

•  Electronic Addressing with Non-volatile memory

 

Permanently stores programmable address, serial number, 
type of device, and job number. Automatically updates historic 
information including hours of operation, last maintenance 
date, number of alarms and troubles, and time and date of last 
alarm.

•  Automatic device mapping

 

Each station transmits wiring information to the loop control-
ler regarding its location with respect to other devices on the 
circuit.

•  Diagnostic LEDs

 

Status LEDs; flashing GREEN shows normal polling; flashing 
RED shows alarm state.

•  Designed for high ambient temperature operation

 

Install in ambient temperatures up to 120 °F (49 °C).

Manual Pull  

Stations

SIGA-270, SIGA-270P,  
SIGA-278

MEA

Patented

SIGA-270 SERIES

7150-1657: 

0129

S2318

Reviews: