ANSREM Remote Microphone Installation Sheet

 

Product description 

The 

ANSREM

 

is a supervised remote microphone panel for 

use with the ANS25, ANS50, and ANS100 audio notification 

system

s. The 

ANSREM

 

makes it possible to send emergency 

voice messages through the system speakers from a location 

that is remote from the ANS panel.

 

The 

ANSREM

 uses 3-

pair shielded cable to connect to 

ANSREMSUP supervisory card, which is mounted within the 

ANS master panel. Fault conditions in the wiring or in the 

remote microphone circuitry are reported to the fire alarm 

control panel (FACP) using the same supervisory path as the 

ANS master panel.

 

Specifications 

Table 1: Specifications 
Model 

ANSREM 

ANSREMSUP 

Input voltage

 

24 Vdc

 

24 Vdc

 

Input current

 

 

Standby

 

 

Active 

 

20 mA

 

40 mA

 

 

30 mA

 

50 mA

 

Wiring

 

12 to 22 AWG

 

12 to 22 AWG

 

Operation 

When the system is in the alarm state, keying the ANSREM

 

microphone interrupts the alarm signal and digital message. 

Live voice messages can then be broadcast over the system.

 

When the system is in normal standby state, the ANSREM

 

microphone can be keyed to make announcements at any 

time.

 

Keying an ANSREM

 

microphone at any time turns on the 

In

 

Use LEDs on all other ANSREMs, and disables the other 

units. This ensures that only one operator is able page over the 

system. If the microphone in the master ANS panel is keyed, it 

overrides all ANSREM

 

microphones.

 

Installation instructions 

Ensure that all wiring and devices installed in the system meet 

the following standards:

 

 

NFPA 70 

National Electrical Code

 

 

NFPA 72 

National Fire Alarm and Signaling Code

 

 

NFPA 101 

Life Safety Code

 

 

Applicable state and local codes

 

Install this equipment in a clean, dry environment. Avoid 

locations where equipment is subjected to vibration. Remove 

all electronic assemblies from the enclosur

before 

drilling or 

punching the enclosure. Where possible, make all cable 

entries from the rear or sides. Before making any modifications 

to the enclosure, be certain that they will not interfere with the 

assemblies.

 

Make sure all power is off before making any wire connections.

 

Terminals 

Table 2: Terminal descriptions 
Terminal [1] 

Description 

TB1

-1 

V+ 24 Vdc 40 mA

 

TB1

-2 

Ckt Neg

 

TB1

-3 

Fault +24 V (pull down 10 mA)

 

TB1

-4 

PTT +24 V 10 mA

 

TB1

-5 

Audio 1 Vrms 10 mA

 

TB2

-1 

MIC PTT +24 V 10 mA

 

TB2

-2 

V+ 24 Vdc 100 mA

 

TB2

-3 

PTT +24 V 10 mA

 

TB2

-4 

Audio 1

 

Vrms 10 mA

 

TB2

-5 

Ckt Neg

 

TB2

-6 

Fault +24 V 10 mA

 

TB2

-7 

Earth Ground

 

[1] TB1 designations are the same for both the ANSREM

 

and 

ANSREMSUP. TB2 is on the ANSREMSUP only.

 