Installation Instructions for Flush Wall Mount Electromagnetic Door

Holders Catalog Series 1509

P/N 3100539  ISSUE 1 © 2003

501-152800-0-01

Description

The 1509 Series are flush mount door holders for use with single

doors.  The units are UL and cUL Listed and FM approved

Installation

Install and wire in accordance with applicable codes, standards,

such as NFPA publications 70 (National Electrical Code), 72 (Na-

tional Fire Alarm Code), and 80 (Standard for Fire Doors and Fire

Windows),  and/or other regulations applicable to the country

and locality of installation and in accordance with authorities

having jurisdiction.

1.

Using Figure 1 and Table 2, locate the intersection of

Dimension X and Dimension Y.  Dimension Z is shown at the

intersection in the gray area.

NOTE:

If dimension X or Y is not shown on the chart,

extrapolate Dimension Z.  (i.e., if X=7, and Y=28,

Z = (27-5/8 - ((27-5/8 - 27-1/4)/2) => Z = 27-9/16"

2.

Install a single gang outlet box (not supplied) on the

horizontal center line and 5" from the top of the door.

NOTE:

The outlet box must be able to withstand a maximum

holding force of 50 pounds.

If X and Y intersect in the blank area in Table 2, DO NOT

install the outlet box.  The contact plate and electromagnet

cannot be aligned with these dimensions.

Door

Door jamb

Wall line

Outlet box

center

line

X

Z

Y

Figure 1.  Locating the Door Holder

Table 2.  Dimension chart (in inches)

Table 1.  Specifications

Cat. No.

Volts

Amps

1509-E1

12V DC

0.170

1509-E5

12V AC 60 Hz

0.150

1509-AQN5

24V AC 60 Hz

0.015

24V DC

0.015

120V AC 60 Hz

0.015

Electromagnet Assembly and Cover Mounting

WARNING

To prevent electrical shock, ensure power is discon-
nected.

1.

Refer to Figure 2.  Pull field wiring through conduit into the

single gang outlet box.

2.

Establish earth-ground continuity in accordance with

applicable codes, standards and authorities having

jurisdiction.  A green insulated lead wire is provided on -

AQN5 models for this purpose.

3

For -E1 and -E5 models, connect the field power wiring to the

electromagnet assembly wiring leads.

For -AQN5 models, refer to Figure 3 and connect as

instructed below:

a.

120V AC operation

.  Connect power field wiring to

terminals marked "120V AC" and "COM."

b.

24V AC/DC operation

.  Connect power field wiring to

terminals marked "24V AC/DC" and "COM."

4.

Secure the electromagnet bracket assembly to the outlet box

using two #6-32 x 1/2" screws provided (Figure 2).

5.

Mount the cover to the electromagnetic bracket assembly

and secure with the two #6-32 x 3/8" screws provided

(Figure 2).

NOTE:

The combined projection of the electromagnet

assembly and armature assembly is 1 27/32".

Armature Assembly Mounting

NOTE:

 Armature assembly must be mounted vertically

(Figure 4) to obtain correct alignment with the

electromagnet.

CHESHIRE, CT  203-699-3300  

CUST. SERV. FAX

  203-699-3365  

TECH SERV. FAX

  203-699-3078

28

30

32

34

36

38

40

42

44

46

48

2

26 (660)

28 (711)

29 7/8 (759)

32 (813)

34 (864)

36 (914)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114) 45 5/8 (1159)

4

26 (660)

28 (711)

29 7/8 (759)

32 (813)

34 (864)

36 (914)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114) 45 5/8 (1159)

6

25 5/8 (651)

27 5/8 (702)

29 5/8 (752)

31 3/4 (806)

33 3/4 (857)

35 3/4 (908)

37 3/4 (959)

39 3/4 (1010) 41 3/4 (1060) 43 5/8 (1108) 45 3/8 (1153)

8

25 1/4 (641)

27 1/4 (692)

29 1/4 (743)

31 3/8 (797)

33 1/2 (851)

35 1/2 (902)

37 3/8 (949)

39 1/2 (1003) 41 1/2 (1054) 43 3/8 (1102) 45 1/4 (1149)

10

24 5/8 (625)

26 3/4 (679)

28 3/4 (730)

30 7/8 (784)

33 (838)

35 (889)

37 (940)

39 1/8 (994)

41 1/8 (1045) 43 (1092)

44 7/8 (1140)

12

23 3/4 (603)

25 7/8 (657)

28 (711)

30 1/8 (765)

32 1/4 (819)

34 3/8 (873)

36 3/8 (924)

38 1/2 (978)

40 5/8 (1032) 42 1/2 (1080) 44 3/8 (1127)

14

23 3/4 (603)

25 (635)

27 1/4 (692)

29 3/8 (746)

31 1/2 (800)

33 3/4 (857)

35 7/8 (911)

38 (965)

40 (1016)

42 (1067)

43 7/8 (1114)

16

21 3/4 (552)

24 (610)

26 1/4 (667)

28 1/2 (724)

30 3/4 (781)

33 (838)

35 1/8 (892)

37 1/4 (946)

39 3/8 (1000) 41 3/8 (1051) 43 3/8 (1102)

18

20 (508)

22 1/2 (572)

25 (635)

27 3/8 (695)

29 3/4 (756)

32 (813)

34 1/4 (870)

36 1/2 (927)

38 5/8 (981)

40 5/8 (1032) 42 1/2 (1080)

20

18 1/4 (463)

21 (533)

23 1/2 (597)

26 (660)

28 1/2 (724)

30 7/8 (784)

33 1/8 (841)

35 3/8 (899)

37 5/8 (956)

39 5/8 (1006) 41 5/8 (1057)

22

18 3/4 (476)

21 5/8 (549)

24 3/8 (619)

27 (686)

29 3/8 (746)

31 3/4 (806)

34 1/8 (867)

36 1/2 (927)

38 5/8 (981)

40 3/4 (1035)

24

22 1/2 (572)

25 1/2 (648)

28 1/8 (714)

30 5/8 (778)

33 1/8 (841)

35 5/8 (905)

37 7/8 (962)

40 (1016)

26

  Do not install outlet box if

26 1/4 (667)

29 (737)

31 5/8 (803)

34 1/4 (870)

36 1/2 (927)

38 5/8 (981)

28

  Dimensions X and Y intersect in this blank area.

29 3/4 (756)

32 1/2 (826)

34 7/8 (886)

37 1/8 (943)

30

  The armature and electromagnet cannot be aligned.

27 3/4 (705)

30 5/8 (778)

33 (838)

35 3/8 (899)

32

31 3/8 (797)

33 7/8 (860)