Installation Instructions for Flush Wall Mount Electromagnetic Door
Holders Catalog Series 1509
P/N 3100539 ISSUE 1 © 2003
501-152800-0-01
Description
The 1509 Series are flush mount door holders for use with single
doors. The units are UL and cUL Listed and FM approved
Installation
Install and wire in accordance with applicable codes, standards,
such as NFPA publications 70 (National Electrical Code), 72 (Na-
tional Fire Alarm Code), and 80 (Standard for Fire Doors and Fire
Windows), and/or other regulations applicable to the country
and locality of installation and in accordance with authorities
having jurisdiction.
1.
Using Figure 1 and Table 2, locate the intersection of
Dimension X and Dimension Y. Dimension Z is shown at the
intersection in the gray area.
NOTE:
If dimension X or Y is not shown on the chart,
extrapolate Dimension Z. (i.e., if X=7, and Y=28,
Z = (27-5/8 - ((27-5/8 - 27-1/4)/2) => Z = 27-9/16"
2.
Install a single gang outlet box (not supplied) on the
horizontal center line and 5" from the top of the door.
NOTE:
The outlet box must be able to withstand a maximum
holding force of 50 pounds.
If X and Y intersect in the blank area in Table 2, DO NOT
install the outlet box. The contact plate and electromagnet
cannot be aligned with these dimensions.
Door
Door jamb
Wall line
Outlet box
center
line
X
Z
Y
Figure 1. Locating the Door Holder
Table 2. Dimension chart (in inches)
Table 1. Specifications
Cat. No.
Volts
Amps
1509-E1
12V DC
0.170
1509-E5
12V AC 60 Hz
0.150
1509-AQN5
24V AC 60 Hz
0.015
24V DC
0.015
120V AC 60 Hz
0.015
Electromagnet Assembly and Cover Mounting
WARNING
To prevent electrical shock, ensure power is discon-
nected.
1.
Refer to Figure 2. Pull field wiring through conduit into the
single gang outlet box.
2.
Establish earth-ground continuity in accordance with
applicable codes, standards and authorities having
jurisdiction. A green insulated lead wire is provided on -
AQN5 models for this purpose.
3
For -E1 and -E5 models, connect the field power wiring to the
electromagnet assembly wiring leads.
For -AQN5 models, refer to Figure 3 and connect as
instructed below:
a.
120V AC operation
. Connect power field wiring to
terminals marked "120V AC" and "COM."
b.
24V AC/DC operation
. Connect power field wiring to
terminals marked "24V AC/DC" and "COM."
4.
Secure the electromagnet bracket assembly to the outlet box
using two #6-32 x 1/2" screws provided (Figure 2).
5.
Mount the cover to the electromagnetic bracket assembly
and secure with the two #6-32 x 3/8" screws provided
(Figure 2).
NOTE:
The combined projection of the electromagnet
assembly and armature assembly is 1 27/32".
Armature Assembly Mounting
NOTE:
Armature assembly must be mounted vertically
(Figure 4) to obtain correct alignment with the
electromagnet.
CHESHIRE, CT 203-699-3300
CUST. SERV. FAX
203-699-3365
TECH SERV. FAX
203-699-3078
28
30
32
34
36
38
40
42
44
46
48
2
26 (660)
28 (711)
29 7/8 (759)
32 (813)
34 (864)
36 (914)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114) 45 5/8 (1159)
4
26 (660)
28 (711)
29 7/8 (759)
32 (813)
34 (864)
36 (914)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114) 45 5/8 (1159)
6
25 5/8 (651)
27 5/8 (702)
29 5/8 (752)
31 3/4 (806)
33 3/4 (857)
35 3/4 (908)
37 3/4 (959)
39 3/4 (1010) 41 3/4 (1060) 43 5/8 (1108) 45 3/8 (1153)
8
25 1/4 (641)
27 1/4 (692)
29 1/4 (743)
31 3/8 (797)
33 1/2 (851)
35 1/2 (902)
37 3/8 (949)
39 1/2 (1003) 41 1/2 (1054) 43 3/8 (1102) 45 1/4 (1149)
10
24 5/8 (625)
26 3/4 (679)
28 3/4 (730)
30 7/8 (784)
33 (838)
35 (889)
37 (940)
39 1/8 (994)
41 1/8 (1045) 43 (1092)
44 7/8 (1140)
12
23 3/4 (603)
25 7/8 (657)
28 (711)
30 1/8 (765)
32 1/4 (819)
34 3/8 (873)
36 3/8 (924)
38 1/2 (978)
40 5/8 (1032) 42 1/2 (1080) 44 3/8 (1127)
14
23 3/4 (603)
25 (635)
27 1/4 (692)
29 3/8 (746)
31 1/2 (800)
33 3/4 (857)
35 7/8 (911)
38 (965)
40 (1016)
42 (1067)
43 7/8 (1114)
16
21 3/4 (552)
24 (610)
26 1/4 (667)
28 1/2 (724)
30 3/4 (781)
33 (838)
35 1/8 (892)
37 1/4 (946)
39 3/8 (1000) 41 3/8 (1051) 43 3/8 (1102)
18
20 (508)
22 1/2 (572)
25 (635)
27 3/8 (695)
29 3/4 (756)
32 (813)
34 1/4 (870)
36 1/2 (927)
38 5/8 (981)
40 5/8 (1032) 42 1/2 (1080)
20
18 1/4 (463)
21 (533)
23 1/2 (597)
26 (660)
28 1/2 (724)
30 7/8 (784)
33 1/8 (841)
35 3/8 (899)
37 5/8 (956)
39 5/8 (1006) 41 5/8 (1057)
22
18 3/4 (476)
21 5/8 (549)
24 3/8 (619)
27 (686)
29 3/8 (746)
31 3/4 (806)
34 1/8 (867)
36 1/2 (927)
38 5/8 (981)
40 3/4 (1035)
24
22 1/2 (572)
25 1/2 (648)
28 1/8 (714)
30 5/8 (778)
33 1/8 (841)
35 5/8 (905)
37 7/8 (962)
40 (1016)
26
Do not install outlet box if
26 1/4 (667)
29 (737)
31 5/8 (803)
34 1/4 (870)
36 1/2 (927)
38 5/8 (981)
28
Dimensions X and Y intersect in this blank area.
29 3/4 (756)
32 1/2 (826)
34 7/8 (886)
37 1/8 (943)
30
The armature and electromagnet cannot be aligned.
27 3/4 (705)
30 5/8 (778)
33 (838)
35 3/8 (899)
32
31 3/8 (797)
33 7/8 (860)