SSM-LE Series
Operations Manual
Eberle Design Inc.
Page 23
LCD Operating Temperature Range ........................................................ -34 to +74
o
C
Humidity Range (non-condensing) ..................................................... 0 to 95% Relative
7.4 TIMING FUNCTIONS
Conflict
No Fault .................................................................................. less than 200 msec
Fault .................................................................................. greater than 450 msec
Typical ................................................................................................... 350 msec
Red Fail
No Fault .................................................................................. less than 700 msec
Fault ................................................................................ greater than 1000 msec
Typical ................................................................................................... 850 msec
Controller Voltage Monitor (CVM)
No Fault .................................................................................. less than 125 msec
Fault .................................................................................. greater than 175 msec
Typical ................................................................................................... 150 msec
+24Vdc Monitor
No Fault .................................................................................. less than 125 msec
Fault .................................................................................. greater than 175 msec
Typical ................................................................................................... 150 msec
Clearance Fail
No Fault ........................................................................... greater than 2.8 second
Fault ..................................................................................... less than 2.6 second
Typical .................................................................................. less than 2.7 second
Dual Indication
No Fault .................................................................................. less than 200 msec
Fault .................................................................................. greater than 500 msec
Typical ................................................................................................... 400 msec
Power Fail
Respond ............................................................................ greater than 500 msec
No Response .......................................................................... less than 450 msec
Typical ................................................................................................... 475 msec
Minimum Flash ........................................................................................ 4 to 15, +
_1 second
Start Delay .................................................................................................. 2.5 +
_0.5 second