Eberle Design Inc. 

Page 5 

Section 2  

MONITOR FUNCTIONS 

2.1 CABINET POWER SUPPLY MONITOR 

The  CMUip-2212  will sense the C48VDC,  +24VDC and +12VDC power supply 

sources. The CMUip-2212 will also sense the C24VDC state as reported by each 

HDSP. Voltages less than the threshold voltages for the Fault time or longer (section 5.2) 

will cause a LFSA. A +48VDC, +24VDC failure or +12VDC failure during the programmed 

Minimum Flash time or during a CMUip-2212  Power Failure will not cause a LFSA. The 

CMUip-2212 will report the value of the +24 VDC and +12 VDC power supply sources in 

the Type 209 response frame. 
There is programming in the Datakey to d12 VDC and 48VDC power  supply 

monitoring. 

2.2 CONFLICTING CHANNELS MONITOR 

For purpose of conflict determination, an active signal on either of the Green/Walk or 

Yellow inputs associated with any of the 32 channels will be considered as that channel 

being active. The Datakey will contain the permissive channel pair programming. 

 

When any conflicting channels are detected as concurrently active for less than the No 

Fault time (section 5.2)  the  CMUip-2212  will not cause a LFSA. When any conflicting 

channels are detected as concurrently active for the Fault time or longer (section 5.2), the 

CMUip-2212 will cause a LFSA. For all other timing in between, the CMUip-2212 may or 

may not cause a LFSA. 

2.3 SERIAL BUS MONITOR 

The CMUip-2212 communicates with both Serial Bus (SB) #1 and #3. In SB #1 the CMUip-

2212 is a Secondary device, polled by the ATC Primary device. On SB #1, the CMUip-2212 

will respond to the Serial Bus #1 Address defined by the ADDRESS 0 and ADDRESS 1 

pins. On SB #3 the CMUip-2212  is the Primary device, polling each HDSP or HDFU 

Secondary device. 

2.3.1 SERIAL BUS #1 ERROR 

The  CMUip-2212  will cause a FSA when a Type 81 or Type 67 Frame has not been 

received from the ATC for greater than the Fault time (section 5.2). The first and second 

failures in a 24-hour period will be a NFSA. The third failure in a 24-hour period will be a 

LFSA-R. If a CMUip-2212 Power Fail resets the LFSA-R, the SB #1 failure count will be 

reset to two, such that the next SB #1 timeout results in a LFSA-R. 
A SB #1 timeout failure during the programmed Minimum Flash time or during a CMUip-

2212 Power Failure will not cause a FSA. The SB #1 Timeout function will be disabled if the 

SB #1 DISABLE input is at a True (Low) state  

2.3.2 SERIAL BUS #3 ERROR 

The  CMUip-2212  will cause a FSA when a Type 129 or Type 130 Frame has not been 

received from each enabled HDSP for greater than the Fault time (section 5.2). The first 

and second failures in a 24-hour period will be a NFSA. The third failure in a 24-hour period 

will be a LFSA-R. If a CMUip-2212 Power Fail resets the LFSA-R, the SB #3 timeout count 

will be reset to two, such that the next SB #3 timeout results in a LFSA-R. 
A SB #3 timeout failure during the programmed Minimum Flash time or during a CMUip-

2212 Power Failure will not cause a FSA.  

Summary of Contents for CMUip-2212 Series

Page 1: ...TOR UNIT Firmware Version 2 0 vXX20 Issue J PCB REVISION MAY 2019 pn 888 2212 001 CMUip 2212 ATCC Cabinet Monitor Unit Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4 5 OR HIGHE...

Page 2: ...ETARY TECHNICAL INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2019 EDI U S Pat No 7 246 037 Can...

Page 3: ...ance Monitor 6 2 8 Yellow Plus Red Clearance Monitor 7 2 9 Local Flash Status 7 2 9 1 Local Flash Status Recovery 7 2 10 Circuit Breaker Trip Status 7 2 11 Flasher Unit Output Failed Alarm 7 2 12 CMU...

Page 4: ...s 1 Address Inputs 16 3 7 Serial Bus 1 Disable input 17 3 8 CMUip 2212 Temperature 17 Section 4 FRONT PANEL DESCRIPTION 18 4 1 Indicators 18 4 1 1 Power Indicator 18 4 1 2 48VDC FAIL Indicator 18 4 1...

Page 5: ...6 1 1 CMUip 2212 HV CMUip 2212 VHV Pin List 25 6 1 2 CMUip 2212 LV Pin List 25 6 2 CMUip 2212 Ethernet LAN Port 26 6 2 1 Ethernet LAN Cable 26...

Page 6: ...roper operation of the cabinet equipment as well as providing important diagnostic functions used for trouble shooting malfunctioning equipment 1 2 CHANNEL CONFIGURATION The CMUip 2212 can be configur...

Page 7: ...CMUip 2212 provides limited operational status Detailed status is obtained through the front panel Ethernet port CMUip 2212 using Eberle Design ECcom Signal Monitor Communications software running on...

Page 8: ...is data allows the CMUip 2212 to better respond to and diagnose fault situations 1 7 1 SERIAL BUS 1 MESSAGE TYPES The CMUip 2212 is compatible with the following message types Type 60 Module Identific...

Page 9: ...Reset Button or EXTERNAL RESET TEST input or a CMUip 2212 Power Fail will reset a LATCHED RESETTABLE FAILED STATE ACTION LFSA R A NONLATCHED FAILED STATE ACTION NFSA will be reset if the fault condit...

Page 10: ...ause a LFSA 2 3 SERIAL BUS MONITOR The CMUip 2212 communicates with both Serial Bus SB 1 and 3 In SB 1 the CMUip 2212 is a Secondary device polled by the ATC Primary device On SB 1 the CMUip 2212 will...

Page 11: ...5 and 16 when Virtual channels are used Lack of Signal Input monitoring will be disabled for all channels when the MC COIL STATUS input is not active There is programming in the Datakey to disable Lac...

Page 12: ...y Unit ADU will display the active field signals This can be helpful to verify that flash mode is active on all outputs appropriately Note that a short time delay will be introduced to the ADU display...

Page 13: ...e high the CMUip 2212 will begin timing the programmed Minimum Flash Interval During the Minimum Flash Interval the CMUip 2212 will be in NFSA 2 12 4 POWER UP Following initial application of MAINS vo...

Page 14: ...triggered the CMUip 2212 to the fault mode and the CMUip 2212 indicates that there is no Field Check Status the ATC or ATC programming is the most likely cause The lack of Field Check Status indicate...

Page 15: ...or pulsing in nature The RMS signal detection algorithm is designed to filter out short term transients commonly found on the electrical service and provide noise immunity against false signal detect...

Page 16: ...PROTECTED TURN CHANNEL The Protected Turn Channel of the FYA channel pair is composed of the solid Green arrow Ga indication of the FYA Signal Output Group 2 16 1 2 PERMISSIVE TURN CHANNEL The Permiss...

Page 17: ...ogramming of the Protected Turn channel Green arrow of the pair 2 16 2 1 2 PERMISSIVE YELLOW CHANGE INTERVAL CONFLICT During the Yellow change interval of the Permissive Turn channel flashing Yellow a...

Page 18: ...rmissive flashing Yellow arrow This allows the CU to sequence from the Permissive Left turn channel directly to the Protected Left Turn channel without a solid Yellow arrow clearance interval 2 16 3 R...

Page 19: ...ough channel is still showing a green ball When the FYA Yellow Trap Conflict condition is detected the CMUip 2212 will enter the fault mode transfer the OUTPUT relay contacts to the Fault position and...

Page 20: ...ill be sensed active when the load current exceeds the programmed Channel LOS Current Sense Threshold programmed for that channel in the Datakey A channel will not be sensed active when the load curre...

Page 21: ...be considered active see Section 5 1 when the door is open These inputs will not be considered active when the door is closed The CMUip 2212 will report the state of these inputs in the Type 209 195 f...

Page 22: ...When the SERIAL BUS 1 DISABLE input is connected to VDC GROUND True The CMUip 2212 will not communicate on Serial Bus 1 or set a FSA condition if communications from the ATC is not present See sectio...

Page 23: ...d The 48VDC 24VDC FAIL and 12VDC FAIL will pulse when either the POWERDOWN or NRESET input is False low See section 2 12 2 4 1 4 12VDC FAIL INDICATOR A red 12VDC FAIL indicator will illuminate when th...

Page 24: ...ator will illuminate when the CMUip 2212 is in FSA as a result of a Serial Bus 3 fault See section 2 3 2 4 1 14 DIAGNOSTIC INDICATOR A red DIAGNOSTIC indicator will illuminate when the CMUip 2212 is i...

Page 25: ...power is applied to the CMU 2212 the CMUip 2212 will continue to use the parameters from the removed Datakey until Reset is applied a new Datakey is installed or a power up cycle occurs If a CMUip 22...

Page 26: ...ss than 77 Vrms DC Control Monitors Local Flash Status MC Coil Status FTR Coil Drive CB Trip Status Active greater than 44 Vdc Not Active less than 42 Vdc Front Rear Door Switch Active greater than 13...

Page 27: ...than 11 Vdc Power Fail Monitor Mains Restore greater than 45 1 Vrms Mains Dropout less than 43 1 Vrms DC Voltage Monitors 48 Volt Monitor Active greater than 46 Vdc Not Active less than 44 Vdc 24 Vol...

Page 28: ...han 164 2 Vrms DC Voltage Monitors 24 Volt Monitor Active greater than 22 Vdc Not Active less than 18 Vdc 12 Volt Monitor Active greater than 11 Vdc Not Active less than 9 Vdc Logic Inputs External Te...

Page 29: ...200 ms Typical 300 ms Circuit Breaker Trip Fault greater than 400 ms No Fault less than 200 ms Typical 350 ms AC Line Level Sense Fault greater than 750 ms No Fault less than 550 ms Typical 650 ms Fla...

Page 30: ...c A16 Nreset B16 Nreset A17 PowerDown B17 PowerDown A18 SB3 TxData B18 SB3 TxData A19 SB3 RxData B19 SB3 RxData A20 SB3 Clock B20 SB3 Clock A21 LF Status B21 LF Status A22 Output Relay NO B22 Output R...

Page 31: ...Rear B28 Reserved A29 Reserved B29 DC MAINS Power A30 Reserved B30 No Connect A31 Equipment Ground B31 Reserved A32 Reserved B32 MAINS Ground Note Output Relay NO is open during FSA de energized 6 2...

Reviews: