2010ECL-NYC SERIES SIGNAL MONITOR 

OPERATIONS MANUAL 

Eberle Design Inc. 

Page 29 

Section 7  

TROUBLE SHOOTING 

SYMPTOMS: 

Will not power on 

CAUSES: 

 A) 

Blown fuse 

 B) 

Internal power supply is low 

 C) 

No AC input to the monitor 

SOLUTIONS: 

 A) 

Remove the fuse and verify with an Ohm meter. Replace if necessary with 
a fuse with the same current rating. 

 B) 

Check  the  unregulated  voltage  across  filter  capacitor  C78  with  an 
oscilloscope or volt meter. It should read approximately 170 Vdc when the 
AC Line is equal to or greater than 110 Vrms. If the regulated supply (VDD) 
is less than 4.5 Vdc the internal power supply monitoring circuit (U17) will 
hold the  MPU in reset  and the  DIAGNOSTIC  indicator  on  the  front panel 
should illuminate. Measure the regulated voltage across capacitor C28. If it 
measures lower than 5 _

+0.5 Vdc the regulated supply may be overloaded 

or shorted to ground. 

 C) 

If  the  fuse  is  not  blown  then  the  monitor  may  not  be  getting  AC  Line  or 
Neutral to the edge connector of the monitor. 

SYMPTOMS: 

Faults when AC power is applied 

CAUSES: 

 A) 

Program card is absent or not seated properly 

 B) 

AC Line level is low 

 C) 

Memory device fault 

 D) 

No internal watchdog pulses 

SOLUTIONS: 

 A) 

The PCA indicator on the front panel will illuminate. Re-insert the program 
card with the diode side of the card facing the front panel slot and depress 
the RESET switch. The rear edge of the program card should be flush with 
the front panel. 

 B) 

Measure  the  AC  Line  voltage  level  with  a  volt  meter.  If  it  is  below  the 
required "drop-out" level, the monitor will transfer the Output relay contacts 
and  enable  the  STOP  TIME  output  to  the  controller.  The  AC  POWER 
indicator on the front panel will flash at a rate of 2 Hz to indicate the "brown-
out" condition. 

 C) 

The memory devices are verified when AC Line power is applied or a Reset 
command  is  issued.  If  a  memory  fault  is  detected  the  MPU  executes  a 
STOP instruction. This causes all MPU activity to cease. Refer to Section 
2.15.  

 D) 

Absence  of  internal  watchdog  pulses  may  be  due  to  the  following 
conditions: the MPU is not executing or completing the program loop or the 
hardware to detect the internal watchdog pulses is not functioning.  Place 
an  oscilloscope  probe  on  U4.2.  If  there  are  no  pulses,  depress  the  front 
panel  reset  switch  to  re-start  the  MPU.  If  the  watchdog  pulses  are  now 
present on U4.2 then trace the remaining pulse detection hardware for the 
required waveforms.  

SYMPTOMS: 

Required channels will not conflict 

Summary of Contents for 2010ECL-NYC

Page 1: ...2010ECLip 2018ECL 2018ECLip Firmware version 16AL43xx REVISION AUGUST 2019 pn 888 2010 115 MODEL 2010ECL NYC RMS Signal Monitor Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4...

Page 2: ...DWARE COMPATIBILITY WITH THE MT 180 MONITOR TESTER RESISTORS R245 AND R219 HAVE BEEN REMOVED TO DISABLE THIS CIRCUIT IF SPECIAL FUNCTION 2 INPUT IS REQUIRED R245 AND R219 75K OHMS 1 4W SHOULD BE INSTA...

Page 3: ...2 15 Memory Test 7 2 16 Watchdog Monitoring Disabled Indicator 8 2 17 Red Failure Monitor Disabled Indicator 8 2 18 Diagnostic Display Mode 210E 2010 8 2 18 1 No Fault Diagnostic Display 8 2 18 2 Fau...

Page 4: ...2 Y VDC FAILED Indicator 24 5 1 3 R WDT ERROR Indicator 24 5 1 4 CONFLICT Indicator 24 5 1 5 RED FAIL Indicator 24 5 1 6 DUAL IND Indicator 24 5 1 7 CLEARANCE Indicator 24 5 1 8 PCA Indicator 25 5 1 9...

Page 5: ...it Connector P1 33 9 1 1 Sixteen Channel 33 9 1 2 Eighteen Channel 34 9 2 Program Card Connector 34 9 2 1 Sixteen Channel 34 9 2 2 Eighteen Channel 35 9 3 Red Interface Connector P8 36 9 4 EIA 232 Con...

Page 6: ...ns January 1989 When triggered by the detection of a fault condition which exists longer than the minimum period the Signal Monitor will enter the fault mode causing the Output relay contacts to close...

Page 7: ...g the Stop Time output to the controller The WDT Latch option see Section 4 5 1 determines whether this WDT Error fault mode is latched through an AC Line brownout or not If the WDT Latch option is no...

Page 8: ...tile EEPROM device is utilized to retain fault status information and event logs in the event of an AC Line power interruption The correct fault indications will be displayed upon restoration of AC Li...

Page 9: ...ed out bulb may be detected as an active signal due to load switch leakage current and may cause a Dual Indication fault Dual Indication Monitoring may also anticipate a possible Conflict in the event...

Page 10: ...e option can be selected see Section 4 5 2 which provides a flash interval of at least 6 seconds and at most 10 seconds in duration following a power up an AC Line interruption or a brownout restore D...

Page 11: ...from 1000 ms minimum to 10 4 seconds maximum Recurrent Pulse detection can be disabled with the RP DISABLE option switch SW3 2 see Section 4 4 2 2 8 EXIT FLASH When the Signal Monitor series exits th...

Page 12: ...DIAGNOSTIC indicator on the front panel will illuminate to indicate a monitor hardware and or firmware failure This type of failure is configured as latching With latching operation only a loss of AC...

Page 13: ...can display the active Green Yellow and Red field status individually To enter this display mode depress and hold the Reset button Each time the Reset button is activated and held the next set of col...

Page 14: ...he model 210E unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed duri...

Page 15: ...he model 210ECL unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed du...

Page 16: ...A channel pair is enabled for FYA operation the Signal Monitor will monitor the FYA logical channel pair for the following fault conditions 2 20 1 1 1 CONFLICT Channel conflicts are detected based on...

Page 17: ...from the solid Green Arrow 13 14 15 16 to the solid Red Arrow 1 2 3 4 without a minimum clearance time on the solid Yellow Arrow 1 2 3 4 when SSM switch 1 2 3 4 is On The fault channel status will be...

Page 18: ...Turn Channels Ga Opposing Through Channels Permissive Turn Channels Ra Ya fYa Green Arrow Signal Driver Source 13 2 1 9 Yellow Ped 14 4 3 10 Yellow Ped 15 6 5 11 Yellow Ped 16 8 7 12 Yellow Ped 2 20...

Page 19: ...ault channel status will also be indicated for the solid Green Arrow channel 9 10 11 12 IF the solid Green Arrow was active The SSM Switch for each 1 3 5 and 7 channel must be in the ON position to en...

Page 20: ...Section 4 4 8 1 2 20 3 FYAC COMPACT MODE H The Model 2010 NYC does support FYA Mode H operation WARNING IF THE PERMISSIVE FLASHING YELLOW ARROW AND PROTECTED GREEN ARROW CHANNEL ASSIGNMENTS ARE SWAPP...

Page 21: ...f operation 3 2 2 EDI ECCOM MONITOR REPORT The EDI ECcom software package Version 3 8 or greater is required interfaces a Computer to the ECL and ECLip models The ECcom program will display the Status...

Page 22: ...Enable Configuration Fault Enable Red Cable Fault enable AC Brownout timing e Watchdog Programming Watchdog Enable Watchdog timing and Watchdog Latch f Configuration Check Value the value of the 16 b...

Page 23: ...Type 01 Firmware V5 0 Comm V3 6 RMS Engine Firmware Type 01 RMS Engine Firmware V2 3 ECcom Version 3 6 2 Downloaded at 10 13 48 AM Friday September 22 2006 Number of events 10 A symbol indicates that...

Page 24: ...lse ENABLED Watchdog Timing 1 5 seconds GY Enable DISABLED FYAC Mode H DISABLED LEDguard Thresholds ENABLED Red Fail Enabled by SSM DISABLED Dual Indication Fault Timing 350 500 ms WDT Error Clear on...

Page 25: ...ction is in hardware flash 4 1 2 SPECIAL FUNCTION PREEMPT INPUTS SF1 SF2 The pins numbered 8 and 6 of Red Interface connector P8 are Special Function SF inputs 1 and 2 respectively NYCDOT These inputs...

Page 26: ...MMING The Signal Monitor provides switch options to modify the monitor operation The Option switches are labeled OPTIONS SW3 and are located near the program card edge connector 4 4 1 RED FAIL TIMING...

Page 27: ...ed through an AC Line brownout or not If the WDT Latch select is not jumpered an AC Line brownout condition will reset the WDT ERROR fault mode when the AC Line is restored The WDT Error indicator wil...

Page 28: ...ates fault or flash mode operation 4 5 7 FYA FLASHRATE MONITOR DISABLE SEL15 The Signal Monitor will respond to an enabled flashing Yellow Arrow signal that is not flashing at a minimum rate see Secti...

Page 29: ...dicator will illuminate when a controller Watchdog fault is detected If the WD ENABLE switch is placed in the OFF position to disable Watchdog monitoring or the AC Line voltage is below the Watchdog d...

Page 30: ...to the DTR signal in the false state while a frame is in the transmit queue 5 1 12 CHANNEL STATUS INDICATORS 210E 2010 During normal operation the 210E 2010 model Channel Status indicators will displ...

Page 31: ...ired inputs for the Signal Monitor to monitor the Red Field Signal outputs It is polarized to insure proper mating with the adapter cable Ejector latches are included to facilitate removal and prevent...

Page 32: ...ed to interconnect the main microprocessor to the following circuit blocks EEprom U21 Real Time Clock U29 24Vdc Logic Processor U41 Display Multiplexer U1 Program Card and Switch inputs U25 4 and the...

Page 33: ...hannel The resulting data is transferred to the main MPU via the SPI interface The analog to digital converter U39 provides the voltage measurement data for the RMS Engine approximately every 6 micros...

Page 34: ...ce fault D No internal watchdog pulses SOLUTIONS A The PCA indicator on the front panel will illuminate Re insert the program card with the diode side of the card facing the front panel slot and depre...

Page 35: ...Eberle Design Inc Page 30 CAUSES Diode on the Program Card is open or absent SOLUTIONS Check the program card to verify that the required diode is in place If the diode is present then verify all conn...

Page 36: ...rms Special Function Inputs no detect less than 50 Vrms detect greater than 70 Vrms Watchdog Enable AC level enable greater than 94 _ 2 Vrms disable less than 91 _ 2 Vrms LEDguard Low Threshold Signal...

Page 37: ...milliseconds typical 1350 milliseconds Dual Indication no fault less than 200 milliseconds fault greater than 500 milliseconds typical 400 milliseconds Dual Indication Long no fault less than 700 mill...

Page 38: ...YELLOW T UNASSIGNED 17 UNASSIGNED U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 UNASSIGNED W UNASSIGNED 20 CHASSIS GROUND X UNASSIGNED 21 AC Y DC GROUND 22 WATCHDOG TIMER Z EXTERNAL R...

Page 39: ...NNEL 11 YELLOW S CHANNEL 11 GREEN 16 CHANNEL 9 YELLOW T CHANNEL 18 YELLOW 17 CHANNEL 18 GREEN U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 CHANNEL 17 RED W CHANNEL 18 RED 20 CHASSIS...

Page 40: ...BIT COMMON FF NO CONNECT Mating connector shall be keyed between pins 24 and 25 and also BB and CC The Monitor circuit and the Program Card mate with a 28 56 pin double sided edge card connector havin...

Page 41: ...NNEL 1 RED 10 CHANNEL 11 RED 20 RED ENABLE Note Pin 4 may be used to connect the monitor chassis to the cabinet CHASSIS GROUND To complete this connection a soldered wire jumper must be placed in loca...

Page 42: ...5 DCD pin H should be connected to 5 pin D on the Controller Unit connector CTS pin M should be connected to RTS pin J on the Controller Unit connector 9 5 ETHERNET LAN PORT The Ethernet port must be...

Page 43: ...2010ECL NYC SERIES SIGNAL MONITOR OPERATIONS MANUAL Eberle Design Inc Page 38...

Reviews: