Q u i c k S t a r t G u i d e
1. Unpack the Switch and Check Contents
10G Top-of-Rack Switch
AS5610-52X
Rack Mounting Kit—Contains two brackets and eight
screws
Grounding Wire (included with DC PSUs only)
Power Cord—either Japan, US, Continental Europe
or UK (included with AC PSUs only)
Console Cable—RJ-45 to DB-9
Documentation—
Quick Start Guide
(this document)
and
Safety and Regulatory Information
Note:
For information on switch software, refer to
www.edge-core.com
.
Switches with part numbers 5610-52X-D*-******** have
switch software pre-loaded on the switch. Software user
documentation can be found at
www.edge-core.com
.
Switches with part numbers 5610-52X-O-******** have the
Open Network Installer Environment software installer pre-
loaded on the switch, but no switch software image.
Information about compatible switch software can be
found at
www.edge-core.com
.
Caution:
The switch includes plug-in power supply and
fan tray modules that are installed into its chassis. All
installed modules must have a matching airflow direction.
That is, all modules must have a front-to-back (F2B) airflow
direction, or all modules must have a back-to-front (B2F)
airflow direction. The airflow direction of PSU and fan tray
modules is indicated by labels on the modules.
2. Mount the Switch
Attach the brackets to the switch.
Use the screws supplied with the rack to secure the switch in
the rack.
Caution:
Installing the switch in a rack requires two
people. One person should position the switch in the rack,
while the other secures it using the rack screws.
装置の吸排気に必要な領域を マニ ュ アル上に規定 し て
い る。
2
1
1
2
3. Ground the Switch
Ensure the rack on which the switch is to be mounted is
properly grounded and in compliance with ETSI ETS 300 253.
Verify that there is a good electrical connection to the
grounding point on the rack (no paint or isolating surface
treatment).
Attach a lug (not provided with AC PSUs) to an 18 AWG
minimum grounding wire (not provided with AC PSUs), and
connect it to the grounding point on the switch rear panel.
Then connect the other end of the wire to rack ground.
Caution:
The earth connection must not be removed
unless all supply connections have been disconnected.
4. Connect Power
Install one or two universal AC or DC power modules in the
switch.
The switch supports up to two PSUs that must have the
same matching airflow direction as the installed fan tray.
Connect an external AC or DC power source to the modules.
5. Verify Switch Operation
Verify basic switch operation by checking the system LEDs.
When operating normally, the PSU1/PSU2, Diag, and Fan
LEDs should all be on green.