1. Unpack the Switch and Check Contents

AS5812-54T

Rack Mounting Kit—2 front-post brackets, 2 rear-post 
brackets, 20 screws, and 2 ear-locking screws

Power Cord (included with AC PSUs only)

Ground Wire (included with DC PSUs only)

Console Cable—RJ-45 to DB-9

DC Power Cable (included with 48 VDC PSU only)

Documentation—

Quick Start Guide

 (this document) 

and 

Safety and Regulatory Information

Note:

 The switch has the Open Network Install 

Environment (ONIE) software installer pre-loaded on the 
switch, but no switch software image. Information about 
compatible switch software can be found at 

www.edge-core.com

.

Caution: 

The switch includes plug-in power supply (PSU) 

and fan tray modules that are installed into its chassis. All 
installed modules must have a matching airflow direction. 
That is, if the installed power modules have a front-to-back 
(F2B) airflow direction, all the installed fan tray modules 
must also have a F2B airflow direction. 

Note:

 The switch drawings in this document are for 

illustration only and may not match your particular switch 
model.

2. Attach the Brackets

Attach each of the front- and rear-post brackets to the 
switch using four of the included bracket screws.

Use an additional two screws to secure each of the rear-post 
brackets at the mid-point on the sides of the switch.

3

1

1

2

1

2

Use the screws and cage nuts supplied with the rack to 
secure the switch in the rack. 

Caution:

 Installing the switch in a rack requires two 

people. One person should position the switch in the rack, 
while the other secures it using the rack screws.

装置の吸排気に必要な領域を マニ ュ アル上に規定 し て
い る 。

3. Adjust Rear-Post Bracket Ears

Lock the position of the rear-post bracket ears using the 
included position-locking screws.
You can also adjust the rear-post bracket ears to fit different 
rack depths from 56 cm to 75 cm.

4. Ground the Switch

Ensure the rack is properly grounded and in compliance 
with ETSI ETS 300 253. Verify that there is a good electrical 
connection to the grounding point on the rack (no paint or 
isolating surface treatment).

Attach the grounding wire #14 AWG to the grounding point 
on the switch rear panel. Then connect the other end of the 
wire to rack ground.
For details on grounding the switch with a 12 VDC PSU in an 
Open Rack, refer to the Edgecore ORSA-1U Open Rack Tray 
Set 

Installation Guide

.

Caution:

 The earth connection must not be removed 

unless all supply connections have been disconnected.

3

1

1

1

2

1

2

E122017-AP-R03

150200001294A

www.edge-core.com

54-Port 10G / 40G Copper Ethernet Switch

AS5812-54T

Q ui c k   St a r t   G u i d e

Summary of Contents for AS-5812-54T-ec

Page 1: ...ket screws Use an additional two screws to secure each of the rear post brackets at the mid point on the sides of the switch 3 1 1 2 1 2 Use the screws and cage nuts supplied with the rack to secure the switch in the rack Caution Installing the switch in a rack requires two people One person should position the switch in the rack while the other secures it using the rack screws 装置の吸排気に必要な領域をマニ ュ ア...

Page 2: ...d pair cable Not required if the NOS installer is located on attached storage Boot the switch Wait for the ONIE software to locate and execute the NOS installer and then wait for the installer to load the NOS software image Subsequent switch boots will bypass ONIE and directly run the NOS software Note For switches with ONIE software pre loaded refer to the network operating system NOS installer a...

Page 3: ...8 VDC 400 Watts DC Input 36 75 VDC 16 A maximum DC Output 5 VDC 0 5 A 12 VDC 33 A 12 VDC PSU PSU 12V 650 DC Input 12 VDC from Open Rack busbar Regulatory Compliances Emissions EN 55032 2012 AC 2013 Class A EN 61000 3 2 2014 EN 61000 3 3 2013 FCC Class A VCCI Class A CE Mark CCC GB 9254 2008 Class A BSMI EMI Standard CNS 13438 2006 Immunity EN 55024 2010 IEC 61000 4 2 2008 IEC 61000 4 3 2006 A1 200...

Page 4: ...流通 过 注意 本文档中的交换机图片仅用于举例说明 不一定 与您的交换机实际外观完全一致 2 安装交换机 使用四个随附的支架螺丝将各个前柱和后柱支架安装到 交换机 使用另外两个螺丝将每个后柱支架固定到交换机侧面上 的中间点 3 1 1 2 1 2 使用机架随附的螺丝和卡式螺母将交换机固定到支架 上 警告 将此交换机安装在机架中时需要两个人 一个人 将交换机放置在机架中 同时另一个人用机架螺丝将其 固定 装置の吸排気に必要な領域をマニ ュ アル上に規定し て いる 3 调整后柱支架吊耳 使用随附的定位螺丝固定后柱支架吊耳的位置 此外 还可以调整后柱支架吊耳以适合不同的机架深 度 范围是 56 cm 到 75 cm 4 对交换机实施接地 请确保对机架正确实施接地 并确保符合 ETSI ETS 300 253 请确认机架上的接地点的电气导通状态良好 确 保没有油漆或绝缘表面处理 将 14 号的 ...

Page 5: ...会亮起绿灯 7 执行初次系统启动 如果网络操作系统 NOS 安装程序位于网络服务器中 应首先使用 5 5e 类或以上双绞线将 RJ 45 管理 Mgmt 端口连接到网络 NOS 安装程序位于相连的存 储装置中时不需要 2 1 1 2 3 2 1 4 1 3 2 4 1 1 1 启动交换机 等待 ONIE 软件找到和执行 NOS 安装程 序 然后等待安装程序加载 NOS 软件映像 以后交换机启动时将跳过 ONIE 而直接运行 NOS 软件 注意 有关 ONIE 软件位置选项和设置的详细信息 请 参见 NOS 安装程序和 NOS 文档 8 连接网线 对于 RJ 45 端口 在 10GBASE T 环境下 请连接 100 ohm 类别 6 6a 或 7 的双绞线 在 100 1000BASE T 环 境下请连接类别 5 或以上的双绞线 将 DAC 缆线连接至 QSFP 插槽 也可先安装好 QSF...

Page 6: ...6 A DC 输出 5 VDC 0 5 A 12 VDC 33 A 12 VDC PSU PSU 12V 650 DC 输入 12 VDC 从开放式机架后方的母线取电 法规符合性 排放 EN 55032 2012 AC 2013 Class A EN 61000 3 2 2014 EN 61000 3 3 2013 FCC Class A VCCI Class A CE Mark CCC GB 9254 2008 Class A BSMI EMI Standard CNS 13438 2006 抗扰性 EN 55024 2010 IEC 61000 4 2 2008 IEC 61000 4 3 2006 A1 2007 A2 2010 IEC 61000 4 4 2012 IEC 61000 4 5 2014 IEC 61000 4 6 2013 IEC 61000 4 8 2009 IE...

Page 7: ...交換器圖片僅供舉例說明 不一定 與您的交換器外觀完全一致 2 安裝交換器 利用四個所附之托架螺絲 將前柱和後柱托架安裝在交 換器上 額外使用兩個螺絲 將後柱托架各別固定在交換器側邊 中間處 3 1 1 2 1 2 使用隨機櫃提供的螺絲及籠罩螺帽 將交換器固定在機 櫃上 注意 需要兩個人 將交換器裝到機櫃上 一人負責固 定交換器在機櫃上之位置 另一人負責用機櫃螺絲固 定 装置の吸排気に必要な領域をマニ ュ アル上に規定し て いる 3 調整後柱托架固定片 利用所附的定位螺絲 鎖緊後柱托架固定片位置 亦可調整後柱托架固定片 以安裝在深度為 56 cm 至 75 cm 不等之機櫃上 4 對交換器實施接地 請確保對機架正確實施接地 並確保符合 ETSI ETS 300 253 請確認機架上的接地點的電氣導通狀態良好 確 保沒有油漆或絕緣表面處理 將 14 號 AWG 接地線連接至交換器背面面板上的...

Page 8: ...U2 Diag 和風扇 LED 會亮起綠燈 2 1 1 2 3 2 1 4 1 3 2 4 1 1 7 執行初次系統啟動 若網路作業系統 NOS 安裝程式位於網路伺服器 先 使用 5 ohm 第 5 類 5e 類或更優之雙絞線電纜 連接 RJ 45 管理 Mgmt 埠至網路 若 NOS 安裝程式位 於所附儲存設備中 則不需要 啟動交換器 等待 ONIE 軟體找尋並執行 NOS 安裝程 式 並等待安裝程式載入 NOS 軟體映像檔 之後交換器啟動時 會跳過 ONIE 直接運行 NOS 軟 體 說明 關於詳細軟體選項及 ONIE 設定說明 請參閱網 路作業系統 NOS 安裝程式及 NOS 文件 8 連接網路線 對於 RJ 45 端口 在 1 0GBASE T 的環境下 請用 100 ohm 類別 6 6a 或 7 雙絞線 在 100 1000BASE T 環境 下使用 5 類或更好的電纜 連接光...

Page 9: ...6 A DC 輸出 5 VDC 0 5 A 12 VDC 33 A 12 VDC PSU PSU 12V 650 DC 輸入 12 VDC 從開放式機架後方的母線取電 法規符合性 排放 EN 55032 2012 AC 2013 Class A EN 61000 3 2 2014 EN 61000 3 3 2013 FCC Class A VCCI Class A CE Mark CCC GB 9254 2008 Class A BSMI EMI Standard CNS 13438 2006 電磁耐受性 EN 55024 2010 IEC 61000 4 2 2008 IEC 61000 4 3 2006 A1 2007 A2 2010 IEC 61000 4 4 2012 IEC 61000 4 5 2014 IEC 61000 4 6 2013 IEC 61000 4 8 2009 ...

Reviews: