background image

25

10 - ELECTRICAL

10.1 Electrical Wiring

If an external electrical source is utilized, the boiler, 

when installed, must be electrically bonded to ground in 

accordance with the requirements of the authority having 

jurisdiction or, in the absence of such requirements, with 

the National Electrical Code, ANSI/NFPA 70, and/or the 

See wiring diagrams on the following pages for 

details.

• J-box and circulator harness are shipped in parts box, 

and may be wired on either side of boiler as desired.

• Electrically bond boiler to ground in accordance with  

requirements of authority having jurisdiction.  

Refer to: USA - National Electrical Code, ANSI/NFPA 

70.

•  Aluminum  wiring/conductors  not  permitted.         

                                                               

10.2 Thermostat Installation

1. 

Use a thermostat with dry contacts which does not pull 

any load from the control.  Use a separate transformer 

for zone valve wiring.

2. 

Thermostat should be installed on inside wall about 

four feet above floor.

3. 

NEVER install thermostat on outside wall. 

4. 

Do not install thermostat where it will be affected by 

drafts, hot or cold pipes, sunlight, lighting fixtures, 

televisions, fireplace, or chimney.

5. 

Check thermostat operation by raising and lowering 

thermostat setting as required to start and stop 

burners.

6. 

Instructions for final adjustment of thermostat 

are packaged with thermostat (adjusting heating 

anticipator, calibration, etc.)

7. 

Thermostat's heat anticipator must be adjusted to 

match total current draw of all controls associated with 

boiler during heating cycle. 

WARNING

Electrical shock hazard.  Turn OFF electrical power 

supply at service panel before making electrical  

connections.  Failure to do so could result in death 

or serious injury.

!

  

WARNING

Fire, electrical shock hazard.  Verify all electrical 

connections are secure. Failure to do so could result 

in death or serious injury.

!

  

8. 

There are two (2) options when using Zone 2 for an 

indirect tank or heating zone using the IC control to 

power the Zone 2 pump:

a.  A Zone 2 wiring kit is available see parts list. This 

plugs into the Molex connector for the Zone 2 pump 

and provides power leads for the pump.

b. 

Cut off the end of the Molex connector and wire the 

Zone 2 pump leads directly using wire nuts or other 

approved electrical connectors.

 PN 240013268 Rev. D  [08/15/2021]

Summary of Contents for Dunkirk DXL-060K

Page 1: ...ATION OPERATION MAINTENANCE MANUAL Models DXL 060K DXL 095K DXL 120K DXL 150K DXL 175K DXL 205K DXL 235K Tested For 100 psi ASME Working Pressure Manufactured by ECR International Inc 2201 Dwyer Avenu...

Page 2: ...Check our website frequently for updates www ecrinternational com Information and specifications outlined in this manual in effect at the time of printing of this manual ECR International reserves the...

Page 3: ...1 8 Vent Damper Installation Instructions 22 8 1 Vent Damper 22 9 Connecting Gas Service 24 9 1 General 24 9 2 Leak Check Gas Piping 24 10 Electrical 25 10 1 Electrical Wiring 25 10 2 Thermostat Insta...

Page 4: ...ue Diameter 4 5 6 6 7 7 7 102 mm 127 mm 152 mm 152 mm 178 mm 178 mm 178 mm Supply Return Tappings 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT Natural Gas Inlet 1 2 NPT 1 2 NP...

Page 5: ...and all requirements before beginning installation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can...

Page 6: ...w your detector s located on each floor of your home Follow your detector s instructions for operation and verification Some instructions for operation and verification Some jurisdictions may by law r...

Page 7: ...nd height 7 Verify floor will support weight of boiler water and equipment 8 Boiler may be installed on combustible floor Do not install boiler on carpeting 9 Do not install where gasoline or other fl...

Page 8: ...Acids Solvents etc Paint Varnish Turpentine etc Cleaning Solvents Hydrochloric acid muriatic acid Cements adhesives and glues Photo processing plants Garages with workshops Furniture refinishing areas...

Page 9: ...d off unused supply tapping IN UPRIGHT POSITION ONLY Drain valve may be located off of unused return tapping using a contractor supplied tee piped right or left side as desired See Figure 4 3 Unused s...

Page 10: ...rge B be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line C have no intervening shutoff valve between safety relief valve and discharge to...

Page 11: ...e size less than 50 micron If the water quality is outside these ranges consult a local water treatment specialist for recommendations If the water is treated do not use petroleum based products or pr...

Page 12: ...onnected to heating coils located in air handling unit exposed to refrigerated air circulation Install flow control valves or other automatic means to prevent gravity circulation of boiler water durin...

Page 13: ...e mounted on system supply side mounting on system return side is also acceptable practice BACK FLOW VALVE PIPING LEGEND Figure 4 4 Circulators Mounted on Supply System Boiler Used In Configuration wi...

Page 14: ...ure 4 5 Bypass Piping With Automatic Mixing Valve BACK FLOW VALVE PIPING LEGEND 4 CONNECTING SUPPLY AND RETURN PIPING PURGE VALVE DRAIN VALVE ASME RELIEF VALVE BACK FLOW VALVE PN 240013268 Rev D 08 15...

Page 15: ...PLY AND RETURN PIPING Figure 4 6 Bypass Piping Fixed Low Temp Only With Zone Valve BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Manually adjust until proper system temperature is reached PN 2400132...

Page 16: ...ING SUPPLY AND RETURN PIPING Figure 4 7 Bypass Piping 4 Way Valve Option With Circulator On Supply side BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE DRAIN VALVE FLOW CONTROL VALVE PN 240013268 Rev...

Page 17: ...4 CONNECTING SUPPLY AND RETURN PIPING Figure 4 8 Single Zone System With DHW Priority BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Back Flow Valve DRAIN VALVE Purge Valve PN 240013268 Rev D 08 15 2...

Page 18: ...1 DHW Pump 12 po 305 mm Distance recommand e Ne d passez pas 12 po 305 mm Note Note Manufacturer requires all domestic hot water DHW installations use an anti scald valve Local codes may require addi...

Page 19: ...Infiltration Rate See Table 5 1 for space with boiler only Use equation for multiple appliances Do not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input Refer to Nati...

Page 20: ...operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 5 Test for spillage at the draft hood relief opening after 5 minutes o...

Page 21: ...onform to requirements of the authority having jurisdiction or in absence of such requirements to The National Fuel Gas Code ANSI Z223 1 NFPA 54 7 4 Vent Pipe Connect draft hood to boiler using 2 scre...

Page 22: ...ccessible for servicing See Figure 8 2 page 22 4 Damper must be in the open position when appliance main burners are operating 5 Boiler is equipped with factory wired harness that plugs into vent damp...

Page 23: ...23 Figure 8 2 Vent Damper Placement Figure 8 3 Vent Damper Position Indicator 8 VENT DAMPER INSTALLATION INSTRUCTIONS PN 240013268 Rev D 08 15 2021...

Page 24: ...INSTALL MANUAL VALVE WITHIN 6 FT 183 cm OF BOILER AND 5 FT 152 cm ABOVE THE FLOOR WHERE REQUIRED BY LOCAL CODES 3 8 cm Minimum Sediment Trap To Gas Control Inlet DANGER Fire Hazard Do not use matches...

Page 25: ...drafts hot or cold pipes sunlight lighting fixtures televisions fireplace or chimney 5 Check thermostat operation by raising and lowering thermostat setting as required to start and stop burners 6 Ins...

Page 26: ...gure 11 1 4200 Fuel Smart Hydrostat IC Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life PN 24...

Page 27: ...27 11 WIRING DIAGRAM Figure 11 2 4200 Fuel Smart Hydrostat IC Control ladder PN 240013268 Rev D 08 15 2021...

Page 28: ...urn clockwise to OFF DO NOT FORCE 5 Call qualified service technician WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or...

Page 29: ...in death or serious injury A Power remains off until boiler water temperature drops below high limit setting B Circulator continues to operate under this condition until thermostat is satisfied 3 In e...

Page 30: ...lamp in flue collector through draft relief opening or flue inspection cover With mirror positioned above burners flue gas passageways can be checked for soot or scale Follow this procedure to clean f...

Page 31: ...r and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating air to boiler and boiler room shall not be restricted or blocked Inspect fac...

Page 32: ...re than plus or minus 0 3 inches water column from specified pressure listed on boiler rating plate 7 Primary air adjustment is not necessary therefore air shutters are not furnished CHECK SAFETY CONT...

Page 33: ...ric service to be 120 Volts 15 Amps 60 Hz The MEA number for the this boiler is 19 79 E 1 Input rating for sea level to 2 000 ft 610m above sea level United States over 2000 ft 610m above sea level Re...

Page 34: ...he ECONOMY dial WARNING Burn and scald hazard Do not add water until boiler has fully cooled Failure to follow these instructions could result in death or serious injury Control LED legend 1 2 3 4 6 E...

Page 35: ...it leakage to ground Replace pilot burner igniter sensor and provide shield if necessary If flame rod or bracket is bent out of position restore to correct position APPENDIX A CONTROL FUNCTION DANGER...

Page 36: ...connect ignition cable STEP 4 Verify pilot and main burner light off 1 Initiate call for heat Turn thermostat above room temperature Ignition sequence may be delayed by thermal purge up to 2 minutes 2...

Page 37: ...d position 4 Return thermostat to desired position 5 Place vent damper in open position to permit burner operation by using HOLD DAMPER OPEN switch located on damper controller 6 Thermostat controls b...

Page 38: ...jumper wire across orange and yellow wires in Molex plug see Figure 4 This will create bypass of the damper boiler should then ignite If boiler ignites Go to section B 4 Vent Damper Troubleshooting G...

Page 39: ...or heat 1 Thermostat not calling for heat 2 Burned out heat anticipator 3 Loose or broken connections 4 Off On operating limit pressure control or low water cut off 5 Off On blocked vent switch or fla...

Page 40: ...tion THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating l...

Reviews: