46
*
See Tables : SECTION 12.2 - Parameters Setting For High Altitude.
NOTE
:
To scroll to parameters
42
and above,
it is necessary to set
P22
to
22
before scrolling up to the parameter.
9 - START UP PROCEDURE
P07
00..02
= No function is associated
03
= This is an input contact for CH request (e.g. trigger phone).
When contact CN2 is closed and Room Thermostat (RT) requiring heat switches burner on.
Note:
verify heating mode is enabled (winter or heat only mode)
04
= This is an input contact for Low Temperature Thermostat (e.g. floor heating system).
When Low Temperature Thermostat connected on CN2 cuts out, burner switches off and display shows
E178
anomaly.
Note:
verify heating mode is enabled (winter or heat only mode)
05
= This is an input contact for external DHW recirculation pump. When contact CN2 is closed the pump
runs for a specific period.
To enable input it is necessary to set parameter
P04 or P05 = 08
and
P69 = 05
.
Pump will run at
P19
minutes (Summer/Winter mode or Only Winter mode) or
P19/2
minutes (only
Summer mode).
00
P09
Manufacturer information
--
P10
Heating set-point setting OT / RT (Open Therm / Room Thermostat 120V~)
00
= with Remote Control (RC) connected, temperature request is RC set-point
01
= Temperature Request is highest set point between RC and PCB
02
= Temperature request is RU setpoint. The RT enable the gas boiler operates
00
P11..P12
Manufacturer information
--
P13
Max. heating output
(0-100%)
100
80
P14
DHW max. output
(0-100%)
100
P15
Min. heating output
(0-100%)
00
P16
Maximum CH set-point (°C)
00
= 176°F (80°C)
01
= 113°F (45°C)
00
P17
Pump overrun time in heating mode
(01-240 minutes)
03
P18
Burner ignition delay in CH mode
(00-10 minutes) - 00=10 seconds
03
P19
Manufacturer information
07
P20
Pump overrun time in DHW mode
(seconds)
30
P21
Anti-legionellosis function
00
= Disabled -
01
= Enabled
00
P22
Manufacturer information
(set “
22
” to display parameters
42
and above
)
00
P23
Maximum DHW set-point temperature
113°-140°F (45°-60°C), Default 49 = 120°F
49
P24
Manufacturer information
35
P25
No water safety device
00
P26..P31
Manufacturer information
--
P32..P41
Diagnostics (See SERVICE Instructions)
--
P44
Temperature unit setting
00
= °C
01
= °F
01
P06
Outdoor temperature sensor input configuration
00
= with outdoor temperature sensor connected, external temperature value has influence to calculate
heating flow temperature set-point
01
= with outdoor temperature sensor connected, display shows external temperature value (no influence)
02…05
= no function is associated
00
9.16 Description Of Parameters: Factory Settings conti.
FACTORY SETTINGS
125-165
150-205
Model
125
150
165
205
P71*
Maximum Fan Speed
Setting
115
220
105
225
RPM
5650
7200
5550
7250
P72*
Minimum Fan Speed
Setting
40
40
43
40
RPM
1150
1150
1180
1150
To calculate fan speeds
Max. Combi
(P71 * 10) + 5000
Max. Heat Only
(P71 * 10) + 4500
Minimum
(P72 * 10) + 750
P78
0-10V Input
0
= Disabled
1
= Temperature Setpoint (3V = minimum setpoint, 10V = maximum setpoint
2
= Power Setpoint (3V = minimum power, 10V = maximum power)
0
240012879 REV A, [01/31/2020]
Summary of Contents for Dunkirk DCBF-125
Page 63: ...61 A 1 MODELS 125 Heat Only APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 64: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240012879 REV A 01 31 2020...
Page 65: ...63 A 2 MODELS 150 Combi APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 66: ...64 A 4 MODELS 205 Combi APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 67: ...65 NOTES 240012879 REV A 01 31 2020...
Page 68: ...66 NOTES 240012879 REV A 01 31 2020...
Page 99: ...29 MODEL 150F Combi 150F FLOOR STANDING COMBI WIRING DIAGRAM PN 240012875 REV A 01 31 2020...
Page 101: ...31 205F FLOOR STANDING COMBI WIRING DIAGRAM MODEL 205F Combi PN 240012875 REV A 01 31 2020...
Page 106: ...36 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240012875 REV A 01 31 2020...
Page 114: ...44 NOTES PN 240012875 REV A 01 31 2020...