T-Surface Sensor                                        

                                                   

 

 

 

 

Wiring Examples:  

Campbell Data Logger (CR1000) 

This section describes how to connect the T-Surface sensor to the widely used Campbell 
data logger CR1000. If you use another data logger, contact us in case you need further 
assistance. The T-Surface sensor can be connected in differential voltage as well  

as  in  single-ended  voltage  mode,  measurement  range  must  be  set  to  2500  mV.  One 
CR1000  can  record  up  to  eight  T-Surface  sensors  in  differential  mode,  or  sixteen  T-
Surface sensors in single-ended mode. 

Differential Voltage Mode T-Surface sensor 

Connection 

Cable Color 

Input Port 

1

st

 T-Surface 

sensor 

V

T-Surface

 

White 

Vx1 

Brown 

1H 

Black 

1L and Signal Ground 

Program Syntax (exemplifying one sensor, with conversion of raw voltage signal in °C) 

 

VoltDiff(T_Soil,1,mV2500,2,True,0,_50Hz,1,0) 

 

T_Soil=(2500-T_Soil)/T_Air*20000 

 

T_Soil=1/(0,000,000233897*LN(0,000000088*LN(T_Soil)^3)-273.15  

 

DL 18 data logger 

Ordered with stereo plug connector, the T-Surface is compatible with our DL 18 data log-
ger. Each T-Surface sensor requires one of the four channels of the DL 18. For further in-
formation on DL 18 configuration for T-Surface sensors, please refer to our DL18 manual.  

Configured  correctly,  sensor  signals  will  be  stored  in  V.  Values  in  °C  can  be  calculated 
from stored measurement values as described in the following section (Excel program for 
data calculation available on request).  

 
5. Manual Data Calculation 

In case that the used logger does not support complex conversion procedures of the raw 
measurement  values,  stored  values  have  to  be  converted  manually  after  data  download 
from the logger (e.g. DL 18 logger).

  

 

The following function applies to convert the analog output signal of the T-Surface sensor 
from 

V into Ω:  

R

ntc

=(V

ex

-V

out

)/V

out

*20000  

where:  
R

ntc

: NTC sensor resistance in 

Ω corresponding to the respective mV measurement signal  

V

ex

: excitation Voltage in V (e.g. for DL 18 logger V

ex 

= 2.5 V)  

V

out

: measured sensor output signal in V, ranging between 0 and V

ex

  

 
The following function applies to convert the analog output signal 

from Ω into °C: 

T (°C)= 1/(a + b(Ln R

ntc

) + c(Ln R

ntc

)^3)-273.15  (Steinhart-Hart equation) 

where: 
T: temperature in °C  

 

R

ntc

: sensor resistance in 

Ω at temperature T 

 

a: coefficient = 1.13075635 E-03 
b: coefficient = 2.33896902 E-04 
c: coefficient = 8.82996895 E-08 