USER MANUAL
EN
05
/ 2
01
8
SERVICE CONTACT:
MODEL:
ecoGEO Basic
ecoGEO Compact
ecoGEO HP
Page 1: ...USER MANUAL EN 05 2018 SERVICE CONTACT MODEL ecoGEO Basic ecoGEO Compact ecoGEO HP...
Page 2: ...0 3 7 List of user menus 42 3 8 Parameter adjustment 43 3 9 ON OFF Menu 43 3 10 CALENDAR Menu 44 3 11 HEATING Menu 44 3 12 COOLING Menu 45 3 13 DHW LEGIONELLA PROT Menu 46 3 14 POOL Menu 47 3 15 INFOR...
Page 3: ...jury resulting from improper use or incorrect installation of the equipment The heat pump must be installed by a licensed installer in accordance with applicable local regulations and in accordance wi...
Page 4: ...rted up The controller monitors a large number of parameters and will produce a warning if any problem arises It is simply necessary to ensure that the installation is checked regularly by an authoris...
Page 5: ...s points of consumption DHW heating etc The transfer of energy from one circuit to another takes place through heat exchangers where the higher temperature fluid transfers heat to the fluid at a lower...
Page 6: ...DHW Auxiliary integrated hot water equipment Another installation option is a 4 kW ecoGEO 1 9 or 6 kW ecoGEO 3 12 and ecoGEO 5 22 electrical resistor in the production circuit This resistor can be use...
Page 7: ...l geothermal brine systems Control of all nothing or modulating external support units Joint management of several parallel heat pumps up to 3 in ecoGEO B C and as many as 6 in ecoGEO HP Simultaneous...
Page 8: ...user menus and to adjust the parameters Figure 3 1 Control panel The general functions of each of the buttons and operation is indicated below The ALARMS menu can be accessed directly from anywhere i...
Page 9: ...nsumption bar is also shown for the compressor and modulating circulator pumps Aerothermal fan activated only for ecoGEO B C versions Brine pump activated Compressor in start up phase Compressor activ...
Page 10: ...he differential of start up temperatures DHW mode The heat pump sends hot water to increase the temperature of the storage tank so it reaches the DHW setpoint temperature as soon as possible This mode...
Page 11: ...peration program determines which operation modes can be activated WINTER program The heat pump does not allow activation of the PASSIVE COLD and ACTIVE COLD operating modes SUMMER program The heat pu...
Page 12: ...functions EMERGENCY status from control panel The heat pump is in emergency status activated manually from the front panel of the controller The compressor cannot be started up but the services can b...
Page 13: ...w desired information Figure 3 3 Browsing through the list of user menus XXXXXX XXXXXX XXXXXX Mon 4 5 7 5 4 5 User menu 8 On Off Schedule Heating User menu 8 On Off Schedule Heating User menu 3 8 Sche...
Page 14: ...s or next screen or to return to the list of user menus Figure 3 4 Adjusting comfort parameters 3 9 ON OFF Menu On Off Shows the direction of the unit Used to switch the heat pump on off or to activat...
Page 15: ...is can be used to program up to 3 periods a year when the heat pump stays on or off 3 11 HEATING Menu Heating This enables the HEATING mode and adjusts the heating cut off temperature The HEATING mode...
Page 16: ...t off temperature Only PASSIVE COOLING can be activated for outside temperatures between passive and active cut off temperatures ACTIVE COOLING activation is only allowed for outside temperatures over...
Page 17: ...active alarms that prevent compressor start up In SUPPORT mode the auxiliary system is activated after the compressor when the latter cannot reach the target DHW storage tank temperature DHW Recircula...
Page 18: ...n menu from the main screen Brine Production This shows the inlet and return temperatures temperature difference current pressure and the percentage of circulator pump regulation in the brine and prod...
Page 19: ...compressor and condenser operation Compressor 2 This displays the registry of compressor hours of operation number of start ups and start up hour ratios It also shows the current temperature of the c...
Page 20: ...EMERGENCY mode when a critical alarm goes off more than 5 times a day In these cases the heat pump can be unblocked from this screen once the problem has been solved Log alarms The heat pump stores t...
Page 21: ...emperature again Indoor room temperature low in HEATING mode high in COOLING mode Incorrect operation program Select the appropriate program HEATING COOLING mode deactivated Activate the HEATING COOLI...
Page 22: ...and the main screen shows If the problem is solved these alarms disappear and the heat pump starts to operate automatically The button flashes red to indicate that the error has been solved The butto...
Page 23: ...ded external protection9 A C25A Maximum consumption2 B0W35 kW A 2 7 11 8 Maximum consumption2 B0W55 kW A 3 8 16 5 Starting current min max 7 A 2 8 5 8 Correction of cosine 0 96 1 Electrical data Three...
Page 24: ...rnal protection9 A C32A Maximum consumption2 B0W35 kW A 4 2 18 6 Maximum consumption2 B0W55 kW A 5 21 7 Starting current min max 7 A 2 8 Correction of cosine 0 96 1 Electrical data Three phase 3 PE 40...
Page 25: ...xternal protection9 A C50A Maximum consumption2 B0W35 kW A 5 6 28 2 Maximum consumption2 B0W55 kW A 7 8 39 2 Starting current min max 7 A 6 1 15 7 Correction of cosine 0 96 1 Electrical data Three pha...
Page 26: ...king fluids Refrigerant R410A amout kg 4 0 4 2 Compressor oil type amout kg POE 3 3 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 2405 to 9830 Produ...
Page 27: ...ids Refrigerant type amout kg R410A 4 7 R410A 5 5 Compressor oil type amout kg POE 3 6 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 3230 to 13195 P...
Page 28: ...fluids Refrigerant type amout kg R410A 8 5 R410A 9 1 Compressor oil type amout kg POE 6 7 Antifreeze fluid recommended for the source4 Propylene glycol Brine nominal flow B0W351 T 3 C l h 4765 to 193...
Page 29: ...document that supports the date of purchase duly stamped and signed from the establishment that made the sale Disclaimer of warranty The warranty does not include product non conformities derived from...
Page 30: ......
Page 31: ...cela 139 36316 Vincios Gondomar Pontevedra Spain Tel 34 986 262 184 34 986 417 700 Fax 34 986 262 186 e mail Info ecoforest es http www ecoforest es The manufacturer reserves the right to make any nec...