NOTE:  The  above  data  is  adapted  to  power  cord  ≤  10m  .If  power  cord  is 

10m,  wire  diameter  must  be 

increased. The signal cable can be extended to 50m at most.   
 

5.3.    Trial after installation

 

  Please check all the wirings carefully before turning on the heat pump. 

5.3.1

Inspection before use 

 

Check  installation  of  the  whole  heat  pump  and  the  pipe  connections  according  to  the  pipe 
connecting drawing; 

 

Check the electric wiring according to the electrical wiring diagram and earthing connection; 

 

Make sure that the main power is well connected; 

 

Check if there is any obstacle in front of the air inlet and outlet of the heat pump 

 

5.3.2

Trial   

 

The user is advised to start the water pump before the heat pump, and turn off the heat pump 
before the water pump for long life circle. 

 

The user should start the water pump, and check for any leakage of water; Power on and press 
the ON/OFF button of the heat pump, and set desired temperature in the 
thermostat.   

 

In order to protect the heat pump, the heat pump is equipped with start delay 
function. When starting the heat pump, the fan will start to run in 3 minutes, in another 
30 seconds, the compressor will start to run.   

 

After pool heat pump starts up, check for any abnormal noise from the heat pump. 

 

Check the temperature setting 

5.4.    Maintenance and winterizing 

5.4.1 Maintenance     

  The maintenance should be carried out once per year by qualified professional technician.   

 

Cut off power supply of the   

heat pump before cleaning, 

examination and repairing . 

Do not touch the electronic 
components until the LED 
 indication lights on PCB turn off. 

 

Please  clean  the  evaporator  with  household 
detergents or clean water, NEVER use gasoline, thinners or any similar fuel. 

 

Check bolts, cables and connections regularly.

 

 
 

Summary of Contents for Fairland INVERX VERTICAL

Page 1: ...to ensure proper use installation and maintenance Ithomis Str 6 Chalandri GR 15231 Athens Greece el 302106715510 302117007269 302117007270 Fax 302106542877 Website www ecofer com gr INSTALLATION USER...

Page 2: ......

Page 3: ...pecification 10 4 Transportation 11 5 Installation and maintenance 11 5 1 Notice before installation 11 5 2 Installation instruction 12 5 3 Trial after installation 15 5 4 Maintenance and winterizing...

Page 4: ...It must be installed or removed by professionals and it is forbidden to dismantle and refit without permission b Don t put obstacles before the air inlet and outlet of the heat pump 2 Installation a T...

Page 5: ...sion of goods c The unit must be far away from any source of fire d Storage place must be bright wide open and good ventilation ventilation equipment is required 4 Maintenance Notice a If maintenance...

Page 6: ...l wrong direction of the water union 1 2 Operating conditions and range ITEMS RANGE Operating range Air temp 15 43 Temp setting heating 18 40 The heat pump will have ideal performance in the operation...

Page 7: ...the heat pump since the titanium heat exchanger inside the heat pump will be damaged 3 Don t put obstacles before the air inlet and outlet of the heat pump 4 Don t put anything into inlet or outlet o...

Page 8: ...y abnormal circumstances occurred e g abnormal noises smells smokes and leakage of electricity switch off the main power immediately and contact your local dealer Don t try to repair the heat pump by...

Page 9: ...ating range Insufficient water flow or pump blocked Power abnormal 2 Operations 2 1 Notice before using For longer service life please ensure water pump is on before heat pump is on and water pump is...

Page 10: ...elect Turbo Smart Silence mode Up Down Adjust set temperature Note Screen lock a If no operation in 30 seconds screen will be locked b When HP is off screen will be dark and 0 will be displayed c Pres...

Page 11: ...mode selection Smart mode as default will be activated when heat pump is on and screen shows Press to enter Turbo mode and screen shows then press to enter Silence mode the screen shows Press again th...

Page 12: ...k the last page 2 3 Daily maintenance and winterizing 2 3 1 Daily Maintenance Please don t forget to cut off power supply of the heat pump Please clean the evaporator with household detergents or clea...

Page 13: ...18 Rated input power kW at air 15 C 0 17 1 66 0 21 1 95 0 26 2 51 0 33 3 08 0 42 3 67 0 46 4 4 0 46 4 4 0 60 5 94 Rated input current A at air 15 C 0 74 7 21 0 91 8 48 1 14 10 9 1 43 13 4 1 82 15 9 2...

Page 14: ...lation and maintenance The heat pump must be installed by a professional team The users are not qualified to install by themselves otherwise the heat pump might be damaged and risky for users safety 5...

Page 15: ...Location and size To avoid air recirculation the heat pump should be installed in a place with good ventilation or should reserve sufficient space for installation and maintenance Please refer to the...

Page 16: ...bottom please pay attention to it Please insert the drainage tube accessory into the hole and clip it well then connect a pipe to drain off the condensation water 5 2 3 Wiring protecting devices and...

Page 17: ...for protecting devices and cable specification MODEL IXR26 IXR36 IXR46 IXR56 IXR66 IXR80 IXR80T IXR110T Breaker Rated Current A 12 0 15 0 19 0 22 5 24 5 28 5 11 3 15 0 Rated Residual Action Current mA...

Page 18: ...long life circle The user should start the water pump and check for any leakage of water Power on and press the ON OFF button of the heat pump and set desired temperature in the thermostat In order to...

Page 19: ...breaker Fan running but with insufficient heating evaporator blocked Remove the obstacles Air outlet blocked Remove the obstacles 3 minutes start delay Wait patiently Display normal but no heating Set...

Page 20: ...oling mode 7 P0 Controller communication failure 8 P1 Water inlet temp sensor failure 9 P2 Water outlet temp sensor failure 10 P3 Gas exhaust temp sensor failure 11 P4 Evaporator coil pipe temp sensor...

Page 21: ...Installation and user manual 18 APPENDIX 1 HEATING PRIORITY WIRING DIAGRAM OPTIONAL...

Page 22: ...Installation and user manual 19 APPENDIX 2 HEATING PRIORITY WIRING DIAGRAM OPTIONAL...

Page 23: ...Installation and user manual 20 APPENDIX 3 HEATING PRIORITY WIRING DIAGRAM OPTIONAL...

Page 24: ...21 Parallel connection with filtration clock Note The installer should connect A parallel with B as above picture To start the water pump condition A or B is connected To stop the water pump both A a...

Page 25: ...Installation and user manual 22 8 Wifi setting 1 APP Download Android mobile please download from iphone please download from 2 Account registration a Registration by Cell phone number Email...

Page 26: ...Installation and user manual 23 b Cell phone number registration 3 Create family Please set family name and choose the room of device...

Page 27: ...y on the screen once Wifi connection success c If connect fails please make sure your network name and password is correct And your router mobile phone and device are as close as possible d Wifi rebin...

Page 28: ...manual 25 5 Operation More share devices Indicate the status of Heating Heating capacity percentage Select The current swimming pool water temperature The setting temperature Timer Select Turbo Smart...

Page 29: ...manual 26 6 Share devices to your family members After binding if your family members also want to control the device Please let your family members register the APP first and then the administrator...

Page 30: ...Installation and user manual 27 Then your family members can log in as below Notice 1 The weather forecast is just for reference 6 APP is subject to updating without notice...

Page 31: ...Installation and user manual 28 Ithomis Str 6 Chalandri GR 15231 Athens Greece el 30210 6715510 30211 7007269 30211 7007270 Fax 302106542877 Website www ecofer com gr...

Reviews: