ESI (Ultra) Service Manual
17/68
2.3
Field Setting
2.3.1
Default display
LED on main control board can display the operating status of outdoor unit (ODU).
SEG1 SEG2 SEG3
7 segment display instructions
SEG1:
Normally blank, but it displays codes “1~9” accordingly if there is damaged sensor and demand
control requirement.
SEG1 Code
Description
Time
0
Software is updating through IoT device
About 5 min
1
High pressure sensor (HP) fault backup running
7 Days
2
Low pressure sensor (LP) fault backup running
7 Days
3
Compressor discharge temperature sensor (TD) fault backup running
7 Days
4
IPM module temperature sensor (TF) fault backup running
7 Days
5
Ambient temperature sensor (TA) fault backup running
120 Days
6
Defrost sensor (TH) fault backup running
90 Days
7
Compressor suction temperature sensor (TS) fault backup running
120 Days
8
Liquid line temperature sensor (TL) fault backup running
120 Days
9
IoT demand response
-
SEG2:
Normally blank, but it will display code accordingly as below if outdoor unit is running under
limited condition.
SEG2 Code
Description
0
Running under high pressure (HP) limit
1
Running under low pressure (LP) limit
2
Running under discharge temperature (TD) limit
3
Running under IPM module temperature (TF) limit
4
Running under compressor current limit
SEG3:
It displays outdoor unit’s operation mode.
SEG3 Code
Description
0
Stop without running signal (Y signal=OFF)
1
Ready to start-up after receiving running signal (Y signal=ON)
*Note
2
Cooling mode
3
Heating mode
4
Oil return
5
Defrost
6
Manually defrost
7
AUTO charge mode in cooling
8
Pump down
Note: Compressor waits 3~6 minutes to restart.