5
Expansions
5.2
Replacing the ecoBatteryModule
Prerequisites
ATTENTION
If an emergency power supply is available, power to the outlets must be shut off here.
ATTENTION
Storing the ecoBatteryModule
•
Store the ecoBatteryModule in a dry place and prevent the ingress of liquids.
•
Do not store objects on the ecoBatteryModule.
ATTENTION
Wear your personal protective equipment.
ATTENTION
Please read the safety notices on the ecoBatteryModule.
INFORMATION
It is recommended that the previous ecoBatteryModules have an SOC of <10% before a
new ecoBatteryModule is installed. If the difference between the existing and newly installed
ecoBatteryModules is high, it will take longer until all have the same SOC.
Procedure
DANGER
Voltage
An electric shock can lead to severe physical injury or death.
•
Switch off the ecoBatterySystem before carrying out any work on it.
°
Turn off the main fuse
°
Make sure power cannot reach the cables.
•
Only open the ecoBatterySystem when work is about to be performed on it.
1. Open the cabinet door.
2. Press the ON/OFF push-button(1).
Figure 7: The ecoBatterySystem control panel
✓
The green light in the ON/OFF push-button (1) goes off.
✓
The entire power supply is interrupted.
TM_ecoBatterySystem_2.2_en-UK
33