4
Installation and commissioning
4.5
Setting up the ecoBatterySystem
The ecoBatterySystem can be set up using the control panel.
Figure 5: The ecoBatterySystem control panel
1 ON/OFF push-button
2 Battery start push-button
3 Operating light
4 Display for error messages and temperature (for details, see chapter 6.1 "Acknowledging
Prerequisites
➯
The ecoBatterySystem is installed.
Procedure
1. Press the ON/OFF push-button (1) to start the ecoEnergyManagementSystem.
2. As soon as the power system protection is displayed (time on display factory-set to 60
seconds), the inverters are ready for action.
3. Press the battery start push-button (2) to switch on the ecoBatteryModule.
The ecoBatteryModule will take a few seconds to start up.
Inverters in the ecoBatterySystem Small
°
The inverters will start up automatically as soon as there is DC power. When an audible
signal sounds, they have started.
Inverters in the ecoBatterySystem Large
°
The inverters need to be started manually one by one. The left side panel in the
ecoBatterySystem needs to be removed to do this. To the left underneath each inverter is
a flip switch that needs to be pressed. When an audible signal sounds, it has started and
the next inverter can be switched on. The side panel can be refitted once all inverters have
been started.
✓
Operating light (3) lights up in green (unless in emergency power mode).
24