39
68
OFF Temperature / T1-T2 for
Max. Modul. Speed
Water pump turn off temperature (in °C):
Defines the water pump turn off temperature threshold
(MUST BE lower than PAR67 value).
69
Anti-Condensation Exit
Temperature
Backwater temperature (in °C):
Defines the backwater temperature threshold if a backwater
temperature bypass pump is used.
Timings
No.
Parameter
Description
70
Heat Up Duration
Heat Up sequence duration (in seconds)
71
Heat Up Temperature Check
Samples
Not user definable
72
Heat Up Temperature Rise
Not user definable
factors PELLETS / WOOD IN USER FUEL MODE
No.
Parameter
Description
73
User Fuel Feeder 1 ON Time
Factor
User fuel mode feeder speed:
Defines the relative feeder speed compared to the default
feeder speed in pellets powered systems:
50
– the feeder in user fuel mode is 50% slower than the
default feeder setting
100
- the feeder in user fuel mode has the same speed as
the default feeder setting
150
- the feeder is 50 % faster
This parameter is set according to the selected pellets type
factory settings. It can be modified.
74
User Fuel Fan 1 Power Factor
User fuel mode FAN1 speed:
Defines the relative FAN1 speed in user fuel mode (see
PAR73).
This parameter is set according to the selected pellets type
factory settings. It can be modified.
75
Wood Fuel Fan 1 Power Factor
Wood fuel mode FAN1 speed:
Defines the relative FAN1 speed in wood fuel mode.
This parameter is set to 100 if the default wood type is used,
or to different values if wood type other than default is
used. It can be modified to further adjust the burning
parameters.
Operation mode
No.
Parameter
Description
76
Selected Configuration
Controller configuration set:
Selects one of 12 predefined controller configurations.
Configuration 13 is custom. We recommend locking this
parameter in the Fumis PC-PRO application to prevent
editing.