E93.1801EN171 HWB installation manual
60
11
CASCADING
Appliance
The Boilers have an internal flue gas valve for an overpressure system
according to the table below.
This device is needed to prevent recirculation of the flue gases.
If separated flue systems cannot be applied, ask a flue gas supplier to
calculate a zero-pressure common flue system.
11.1.1
C
ALCULATION
HWB
(V
ALID FOR PARTS SUPPLIED BY
D
URAVENT
(M&G)).
Maximum vertical length in feet (m).
Type of
boiler
Number of
appliances
DN150
DN150/200
DN200
DN200/300
HWB-299
3
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
4
36 ft (11 m)
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
5
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
6
16 ft (5 m)
100 ft (30 m)
100 ft (30 m)
HWB-399
3
85 ft (26 m)
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
4
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
5
16 ft (5 m)
100 ft (30 m)
100 ft (30 m)
6
100 ft (30 m)
100 ft (30 m)
CHB-499
3
100 ft (30 m)
100 ft (30 m)
100 ft (30 m)
4
65 ft (20 m)
100 ft (30 m)
100 ft (30 m)
5
20 ft (6 m)
100 ft (30 m)
6
100 ft (30 m)
Remark 1: Dn 150/200 means: the diameter of the horizontal collector including the bend = 150 mm and after
the bend the diameter of the vertical section is 200 mm with an adaptor of 150->200 mm
Remark 2: Length between shaft and last collector (no. A) = 3.3 ft (1 m).
Remark 3: For calculating other lengths between the last collector and the bend, the length of the vertical
height must be reduced by the number of length and for bends the table below must be used.
11.1.2
T
ERMINALS EQUIVALENT FEET
Diameter
Elbow type
DN150
DN200
45°
5.6 ft (1.7 m)
12.5 ft (3.8 m)
90°
13.2 ft (4.0 m)
19 ft (5.8 m)
Summary of Contents for HWB-299
Page 2: ......
Page 7: ...E93 1801EN171 HWB installation manual 7 1 SAFETY GUIDELINES...
Page 8: ...E93 1801EN171 HWB installation manual 8 CONSIGNES DE S CURIT...
Page 65: ...E93 1801EN171 HWB installation manual 65 Ladder Logic Diagram...
Page 66: ...E93 1801EN171 HWB installation manual 66 Electrical schematics...
Page 67: ...E93 1801EN171 HWB installation manual 67...
Page 119: ...E93 1801EN171 HWB installation manual 119 22 SPARE PARTS...
Page 120: ...E93 1801EN171 HWB installation manual 120 68 68 73...
Page 123: ......