E93.1803.901 HW
63
10.1.11
E
XAMPLE
F:
S
EPARATE AIR SUPPLY DUCT
&
FLUE DUCT IN DIFFERENT PRESSURE ZONE
(C53)
Calculation example with given lengths: checking resistance
Boiler type:
CB 105
FL
U
E
Diameter: 100 mm.
quantity
Pa
Pa total
Straight tube m
total
6
4.0
24.0
Bend
45°
2
9.0
18.0
Bend
90°
2
14.5
29.0
Flue outlet
zeta = 1.0
roof
1
15.3
15.3
resistance flue gas outlet:
86.3
A
IR
Diameter: 100 mm.
quantity
Pa
Pa total
Straight tube m
total
2
4.6
9.2
Bend
90°
1
16.8
16.8
Air inlet zeta = 1.0
wall
1
17.7
17.7
resistance air supply:
43.7
Total resistance flue gas outlet and air supply:
130.0
The total resistance is less than 200 Pa.
This flue gas / air supply system is functional.
NOTE: ECO specific resistance values are used in this example.
Flue and air pipes of other suppliers can have other values
Example F maximum pipe lengths
Example F (C53)
boiler type
→
CB 85
CB 105
CB 125
CB 155
Diameter wall terminal
[mm]
100
100
100
150
Diameter air pipe
[mm]
100
100
100
150
Diameter flue pipe
[mm]
100
100
100
150
Diameter roof terminal
[mm]
100
100
100
150
Maximum pipe length [m]
(flue & air total pipe length)
includes: air inlet zeta =1.0
3 bends 90°
2 bends 45°
flue outlet zeta = 1.0
41.1
22.4
7.8
111.1
FLUE OUTLET
AIR INLET
EXAMPLE: F
C53
Summary of Contents for CB 105 HW
Page 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Page 70: ...E93 1803 901 HW 71...
Page 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Page 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Page 128: ...E93 1803 901 HW 129...
Page 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Page 130: ...E93 1803 901 HW 131...
Page 145: ......
Page 146: ......