E93.1803.901 HW
47
A few examples of flue gas material suitable for ECO boilers:
CE String for Plastic PPs: EN14471 T120 P1 W 2 O(30) I C/E L
CE String for Stainless Steel: EN1856-1 T250 P1 W V2-L50040 O (50)
When selecting flue gas systems, be aware that the minimum requirements are met. So only select flue gas
materials having the same or better properties than this table.
WARNING:
Never use aluminum containing flue gas pipes in these boilers.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any
other appliance.
Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.
Connecting diameters and tolerances:
mat
boiler
d
nom
[mm]
D
outside
[mm]
d
inside
[mm]
L
insert
[mm]
St.St.
CB 85, CB 105, CB 125
100
100 +0.3/ -0.7
101 +0.3/ -0.3
50 +2/ -2
St.St.
CB 155
150
150 +0.3/ -0.7
151 +0.5/ -0.5
50 +2/ -2
PP
CB 85, CB 105, CB 125
100
100 +0.6/ -0.6
50 +20/ -2
PP
CB 155
150
150 +0.9/ -0.9
50 +20/ -2
Multiple boilers can be connected to a common duct. These flue gas systems for multiple water heater installations
must always be engineered as zero or negative pressure systems; this to prevent the risk of recirculation of the
flue gases. Consult the flue gas supplier for detailed information and engineering. See also the cascade chapter
for these multiple water heater installations.
READ THE MANUAL PROVIDED BY THE VENT GAS AND AIR SYSTEM SUPPLIER CARE-
FULLY
Polypropylene
This product has been approved for use with polypropylene vent with the manufacturers listed.
All terminations must comply with listed options in this manual and be a single-wall vent offering.
For support and special connections required, see the manufacturer's instructions.
All vent is to conform to standard diameter and equivalent length requirements established.
10.1.1
F
LEXIBLE POLYPROPYLENE
For use of flex pipe, it is recommended to have the vent material in 0 °C or higher ambient space before bending
at installation. No bends must be made to greater than 45° and ONLY installed in vertical or near vertical installa-
tions.
Stainless steel vent.
This product has been approved for use with stainless steel using the manufacturers listed.
Use only the materials and vent systems listed.
DO NOT mix vent systems of different types or manufacturers. Failure to comply could result
in severe personal injury or substantial property damage.
Installations must comply with applicable national, state, and local codes.
Installation of a stainless-steel vent system must adhere to the stainless-steel vent manu-
facturer’s installation instructions supplied with the vent system.
Air supply
When an air supply duct is connected from the outside of the building to the boiler, the water heater will operate
as a room-independent water heater(closed boiler).
NOTICE
WARNING
NOTICE
Summary of Contents for CB 105 HW
Page 69: ...E93 1803 901 HW 70 12 6 Electrical schematic...
Page 70: ...E93 1803 901 HW 71...
Page 71: ...E93 1803 901 HW 72 12 7 Ladder Logic Diagram LOW MAINS VOLTAGE VOLTAGE...
Page 127: ...E93 1803 901 HW 128 22 SPARE PARTS CB 85 HW CB 105 HW and CB 125 HW exploded view...
Page 128: ...E93 1803 901 HW 129...
Page 129: ...E93 1803 901 HW 130 CB 155 HW exploded view...
Page 130: ...E93 1803 901 HW 131...
Page 145: ......
Page 146: ......