
92
Procedure:
1).Confirm that both the 2-way and 3-way
valves are open.
2). Connect the vacuum pump to 3-
way valve’s
service port.
3). Conduct an evacuation for approximately
one hour. Confirm that the compound meter
displays a value of -0.1Mpa(14.5Psi).
4). Close the valve (Low side) on the charge set,
turn off the vacuum pump. After 5 minutes,
confirm that the gauge needle is not moving.
5). Disconnect the charge hose from the
vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging
cylinder. Open the 2-way 3-way valve.
With the charge hose you disconnected from
the vacuum pump, connect it to the valve at the
bottom of the cylinder. If the refrigerant is
R410A, place the cylinder bottom-up to ensure
liquid charge.
2). To purge the air from the charge hose, open
the valve at the bottom of the cylinder and press
the check valve on the charge set (be careful of
the liquid refrigerant).
3) Place the charging cylinder onto the
electronic scale and record the weight.
4). Open the valves (Low side) on the charge
set and charge the system with liquid refrigerant
If the system cannot be charged with the
specified amount of refrigerant, or can be
charged with a only a small amount at a time
(approximately 150g each time),turn the unit on
in cooling mode; however, one time is not
sufficient, wait approximately 1 minute and then
repeat the procedure.
5).If the electronic scale displays the proper
weight, disconnect the charge hose from the
3-
way valve’s service port immediately.
If the system has been charged with liquid
refrigerant while the air conditioner is on, turn
off the air conditioner before disconnecting the
hose.
6). Mount the valve stem caps and the service
port.
Use a torque wrench to tighten the service port
cap to a torque of 18N.m.
Be sure to check for gas leakage.
13.5 Drainage pipe installation
Install the drainage pipe as shown below and
take
measures
against
condensation.
Improperly installation could lead to leakage
and eventually wet furniture and belongings.
13.5.1 Installation principle
Ensure at least 1/100 slope of the drainage
pipe
Adopt suitable pipe diameter
Adopt nearby condensate water discharge
13.5.2 Key points of drainage water pipe
installation
1.
Considering the pipeline route and
elevation
Before installing condensate water pipeline,
determine its route and elevation to avoid
Summary of Contents for CTBU-09HWFN1-M(C)
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units...
Page 9: ...6 A5 Duct Units A6 Duct Units...
Page 10: ...7 Console Units...
Page 11: ...8 Ceiling floor Units...
Page 12: ...9 HESP DUCT Units...
Page 21: ...18 2 3 4 7 Outside Water Pump for Optional When Ceiling Installation...
Page 29: ...26 Console Units 1 6 D ra in p ip e 1 9 5 H a n g in g a rm U n it m m 7 0 0 6 0 0 2 1 0...
Page 36: ...33 Console Units Ceiling floor Units...
Page 41: ...38 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D...
Page 42: ...39 CTBU 36HWFN1 M C CTBU 48HWFN1 M C...
Page 43: ...40 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C...
Page 44: ...41 MUE 48HRFN1 M C MUE 60HRFN1 MW...
Page 45: ...42 MUE 36HRFN1 M C MUE 48HRFN1 M C...
Page 46: ...43 MUE 60HRFN1 MW MTIU 09HWFN1 M MTIU 12HWFN1 M MTIU 18HWFN1 M MTIU 24HWFN1 M...
Page 49: ...46 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W...
Page 50: ...47 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W...
Page 51: ...48 MOD30U 36HFN1 M...
Page 57: ...54 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 58: ...55 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 59: ...56 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 60: ...57 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 61: ...58 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 62: ...59 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4...
Page 78: ...75 12 Field Wiring 9K 24K 36K 48K 60K...
Page 79: ...76...
Page 129: ...126 P U P V...
Page 130: ...127 P W P N...
Page 147: ...144...
Page 193: ...190 5 Remove the four fixing screws of the fan motor then remove the motor 5...