Eclipse ThermJet TJSR0020 Installation Manual Download Page 10

10

Eclipse ThermJet Self-Recuperative, V5, Installation Guide 208, 2/4/2013

Figure 3.10 Flame Sensor Installation

Step 7: Piping

Install the piping as shown in the schematics. Refer to
Chapter 3 of the Design Guide No. 208.

Support the Piping

Use brackets or hangers to support the gas piping. If you
have questions, consult your local gas company.

Straight Run of Pipe Before a Metering Orifice

NOTE:

 There must be a run of pipe with a straight length

of at least 10 pipe diameters before the burner metering
orifice. Failure to provide this length will result in
inaccurate pressure readings, and poor burner operation.

Pipe Connections

Install a pipe union in the gas line to the burner. This
simplifies removal of the burner.

NOTE:

 Flexible pipe nipples will cause inaccurate

metering orifice readings if installed in the burner inlet and
may cause higher pressure drops than equivalent
standard pipe. Consider this when sizing the gas lines.

Avoid Large Pressure Drops

NOTE:

 Pressure drop in the piping is a critical parameter.

Make sure that the size of all the piping is large enough to
prevent excessive pressure losses.

Eductor

NOTE:

 There should be no direct pipe connection to the

eductor outlet. This may effect eductor performance.
There should be at least a 2 inch (50mm) gap between the
eductor outlet and the exhaust duct or cowl.

Step 8: Pressure Taps

There are two sets of air and gas pressure taps for
differential pressure measurements. In addition, there is a
static air pressure tap that can be used to verify air
pressure.

Valves

Valve Orientation

Install all the valves in such a way that the arrow (if
present) on the valve body points in the direction of flow.

Figure 3.11 Valve Orientation

Gas Cocks

Make sure that the handle of a gas cock is at a right angle
to the valve body when the valve is in the closed position.
This is an important position indicator.

Balancing Valves

A gas balancing valve is either an adjustable limiting

orifice valve or a manual butterfly valve. An air balancing
valve is typically a manual butterfly valve. For more
information, refer to the following sections.

Manual Butterfly Valves

• Install manual butterfly valves in accordance with

Bulletin / Info Guide 720.

Adjustable Limiting Orifice Valves

• Install  adjustable  limiting  orifice  valves  in

accordance with Bulletin 728/730.

NOTE:

 It is recommended that there is a run of pipe with

a length of at least 10 pipe diameters between any flow
altering device and the metering orifice on the burner.

Automatic Butterfly Valve

An automatic butterfly valve is driven by an actuator

(actuator and mounting bracket not illustrated).

• Install the control valve in accordance with Bulletin/

Info Guide 720.

Figure 3.12 Butterfly Valves

Ratio Regulator

Connect an impulse line to the ratio regulator and to the
air supply line.

NOTE:

 All settings in this document assume the use of a

Dungs FRG Ratio Regulator. Use of a different Ratio
Regulator may result in improper burner operation.

UV Scanner Location

Flame Sensor;

UV Scanner

 

Closed

Open

Manual

Automatic

Summary of Contents for ThermJet TJSR0020

Page 1: ...Eclipse ThermJet Self Recuperative Burners Models TJSR0020 TJSR0100 Installation Guide 208 2 4 2013 Version 5 ...

Page 2: ... and Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection with the sale installation use of inability to use or the repair or replacement of Eclipse s products Any operation expressly prohibited in this manual any adjustment or assembly procedures not recom...

Page 3: ...duction 6 Handling Storage 6 Position of Components 6 Approval of Components 6 Checklist Before Installation 7 Prepare the Burner 7 Furnace Wall Preparation 7 Burner Installation 8 Valves 10 Checklist After Installation 11 Prepare for Adjustment 11 4 Adjustment Start Stop 12 Introduction 12 Adjustment Procedure 12 Normal Operation Post Commissioning 15 5 Maintenance Troubleshooting 16 Introduction...

Page 4: ...burner system These aspects are Installation Use Maintenance Safety The audience is expected to be qualified and have experience with this type of equipment and its working environment Purpose The purpose of this manual is to make sure that you carry out the installation of a safe effective and trouble free system ThermJet Self Recuperative Documents Installation Guide No 208 This document Datashe...

Page 5: ...ts boards or gaskets Despite these efforts dust created by sanding sawing grinding cutting and other construction activities could release crystalline silica Crystalline silica is known to cause cancer and health risks from the exposure to these chemicals vary depending on the frequency and length of exposure to these chemicals To reduce the risk limit exposure to these chemicals work in a well ve...

Page 6: ...safety by an independent testing agency Typical application examples include American NFPA 86 with listing marks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All the electrical wiring must comply with all applicable local codes and or standards such as NFPA Standard 70 IEC60364 CSA C22 BS7671 Gas Piping All the gas piping must comply with all applicable...

Page 7: ...damaging corrosive gases in the air Prevent direct exposure to water Prepare the Burner Several components must be installed on a burner before it can operate Install the igniter in the burner before installing the burner See Step 5 Igniter and Flame Sensor Installation Furnace Wall Preparation Make sure the furnace wall is capable of supporting the weight of the burner to be installed If necessar...

Page 8: ...de exhaust tube through mounting extension flange into the furnace 3 Place gasket b against exhaust tube flange Use adhesive spray to hold gaskets in place See Figure 3 4 4 Gently place the adapter ring over the flange of the exhaust tube The recess on the adapter ring must face the exhaust tube flange The adapter ring should sit flush with the mounting extension 5 Bolt adapter ring to mounting ex...

Page 9: ...ir inlet housing and into the combustor assembly See Figure 3 9 4 Assemble the rear cover to the air inlet housing using cap screws Torque to 5 ft lbs 7 Nm Position cover so gas inlet is aligned with gas manifold piping Figure 3 7 Figure 3 8 Figure 3 9 Step 6 UV Flame Sensing 1 Install the flame sensor into the designated opening in the rear cover See corresponding datasheet series 208 for proper ...

Page 10: ...tial pressure measurements In addition there is a static air pressure tap that can be used to verify air pressure Valves Valve Orientation Install all the valves in such a way that the arrow if present on the valve body points in the direction of flow Figure 3 11 Valve Orientation Gas Cocks Make sure that the handle of a gas cock is at a right angle to the valve body when the valve is in the close...

Page 11: ...ower to rotate in the proper direction 5 Be sure all valves are installed in the proper location and correctly oriented relative to the flow direction Prepare for Adjustment After installation of the burner system components is complete the following steps should be followed in order to prepare for adjustment 1 Set the air pressure switch so that it drops out at 4 w c 10 mbar below the pressure ra...

Page 12: ...t gas would exit through an auxiliary flue with furnace pressure control The datasheet provides the Eductor butterfly valve settings to be used for both methods and different chamber temperatures Set the integral butterfly valve to the appropriate position for the desired chamber temperature and exhaust requirement See the appropriate datasheet in series 208 To adjust the integral butterfly valve ...

Page 13: ...plicable 1 Set the system to low fire 2 Connect the manometer to Taps A and C air orifice pressure differential 3 Adjust the minimum setting at the automatic zone air control valve until the low fire air differential pressure between taps A and C matches the Minimum Low Fire Air Pressure Drop in the datasheet This is the initial setting only Further adjustment may be required 4 Repeat steps 2 and ...

Page 14: ...ecked at high fire Check the air differential pressure tap A to C If necessary adjust the valve to achieve the desired pressure On multi burner systems check the differential pressure A to C on all burners If the difference in pressure is greater than 0 5 w c 1 25 mbar it will be necessary to adjust the air balance using the valve Check the differential gas pressure tap B to D at each burner if ne...

Page 15: ... fires and explosions Do not touch the ignition plug or the ignition wire when the ignition is on You will get a shock Stop Procedure 1 Close the following valves The manual gas cock for each burner or zone The manual gas cock at the main control valve All the manual shut off valves in the gas line upstream of the burner gas cock 2 Let the burners cool down Keep the blower on until the chamber tem...

Page 16: ...signals 5 Check ignition spark plugs 6 Check valve motors and control valves for free smooth action and adjustment 7 Check for proper operation of the ventilating equipment 8 Test the interlock sequence of all safety equipment manually make each interlock fail noting that related equipment closes or stops as specified by the manufacturer 9 Test flame monitoring control system by manually shutting ...

Page 17: ...er Restore power to the ignition transformer Check flame monitor controller No ignition Open circuit between the ignition transformer and the spark plug Repair or replace the wiring and connectors to the spark plug Check ground connection to the transformer No ignition The spark plug needs cleaning Clean the spark plug No ignition The spark plug is not correctly grounded to the burner Clean the th...

Page 18: ...e burner is erratic and does not respond to adjustment Flame signal weak Check condition of flame monitoring device Internal damage to the burner Some parts inside the burner may be loose or dirty Contact your Eclipse Combustion representative or the Eclipse factory The burner is unstable or produces soot or smoke The air gas ratio is out of adjustment Measure all the gas pressures and air pressur...

Page 19: ...ter mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From To Multiply By actual cubic foot h acfh actual cubic meter h am h 2 832 x 10 2 standard cubic foot h scfh normal cubic meter h Nm h 2 629 x 10 2 degrees Fahrenheit F degrees Celsius C F 32 x 5 9 pou...

Page 20: ...Installation Guide 208 2 4 2013 ...

Reviews: