Eclipse 200 LT valves are manually opening valves that

automatically shut off the gas supply to a combustion sys-
tem when any interlocking limit switch opens. The valve
handle cannot be reset until the condition causing the
open switch is corrected and all limit switches are closed.
Typical limit switches include air pressure, gas pressure,
temperature limit, and flame monitoring contacts. In the
event of a power failure, the valve immediately closes.

Series 200 LT valves include two visual indicators of

“open” or “closed” position: a red “flag” visible in the plastic
dome on top of the valve; and the reset handle position as
indicated by cast markings on the operator case. These
valves also include two SPDT micro-switches that can be
used for auxiliary circuits. Two contacts are made when
the valve opens, and two are made when the valve is
closed.

1.0 Materials of Construction

1.1

Operator housing—

heat treated cast aluminum.

1.2

Valve body—

cast aluminum or cast iron depending

on model selected.

1.3

Valve disc—

steel with Hycar synthetic rubber

bonded to provide soft seating on valve port.

1.4

Valve shaft—

stainless steel.

1.5

Closing spring—

stainless steel.

1.6

Main shaft gas seal—

plated steel with O-ring.

1.7

Main housing and terminal strip—

tightly sealed

using nitrile (UL listed) gaskets in order to assure a
raintight enclosure.

Locktite Manual Reset

Gas Shut-Off Valves

Series 200 LT

10/25/2004

Instruction Manual 750

U.S. Patent No. 3,259,357

Canadian Patent No. 764,833

LISTED 326R

CGA 3.9
CSA 6.5 / ANSI Z21.21

Summary of Contents for 200 LT Series

Page 1: ... operator case These valves also include two SPDT micro switches that can be used for auxiliary circuits Two contacts are made when the valve opens and two are made when the valve is closed 1 0 Materials of Construction 1 1 Operator housing heat treated cast aluminum 1 2 Valve body cast aluminum or cast iron depending on model selected 1 3 Valve disc steel with Hycar synthetic rubber bonded to pro...

Page 2: ... volts A C 3 0 Pressure Taps Position Indicators 2 6 LT valves are agency listed as follows UL listed for air natural gas LP gas hydrogen FM approved for natural LP manufactured gases CSA approved for natural LP mixed and manufac tured gases For wet or corrosive gases such as coke oven or di gester gas corrosion resistant trim must be installed at Eclipse Be sure your valve was ordered to suit you...

Page 3: ...4 4 Wiring diagrams for the latching solenoid and microswitch es are located on the inside surface of the terminal block cover and also in Figure 4 4 5 The operator has two 1 2 threaded conduit con nections for field wiring Use wiring suitable for 75 C operation 4 6 For raintight applications wiring connections to the valve must be made with 90 close ell rigid conduit fittings The conduit should t...

Page 4: ...and move the handle to the open position Look at the visual indicator to verify that the valve is open Do not remove power during the following steps 7 4 Loosen and remove the 8 hex head bolts holding the operator to the valve body 7 5 Carefully lift the operator straight up until the stem clears the body 7 6 Inspect the gasket for any problem that may lead to gas leakage If any problem is detecte...

Reviews: