
Firmware V1.4
20.05.2021
45/113
5.12 Service Area Analogue Inputs and Outputs
For test and service purposes, all analogue inputs and outputs of the controller can be manually overridden in
manual mode. The service area is password-protected and must be activated beforehand.
Activation of the service area via password
The password (PW) for the service area (service mode) is entered in the "General" area (grey field) on the
"Setpoints HT LT power signal" page:
The password is 65205 and cannot be changed.
If the controller has accepted the password, "0" is displayed again in the input field for security
reasons. The green indicator light underneath signals that the service area is active (enabled). After
10
minutes without
manual override at the analogue inputs and outputs, the service area is blocked
again. For another manual override, the password must be entered again.