KGL Operating Manual – VS 3010 BS
2018-07-02
/
22 178
Cascade Mode
If required, the pack controller can be used to control a cascade compressor pack; for further details, see
chapter
Layout of a system with cascade:
4.3 Configuration of the pressure transducers
The pack controller operates with continuous pressure transducers with linear characteristic. The pressure
inputs can be adjusted for various transducers with linear characteristic. Both transducers with current output
(4..20 mA) as well as those with voltage output (0…10 V) can be used here.
For transmitters with voltage output, the corresponding jumpers must be implemented on the
controller (see chapter
Configuration of the analogue inputs and outputs, page 90
preconfigured as 4..20 mA current inputs at the factory.
The pressure transducers can be adjusted in menu 3-1-a using the following parameters: