Firmware V7.16.x
16.05.2023
29/183
5.5 Digital inputs
The digital inputs can be configured for monitoring and alarm signalling of external maintenance groups /
external alarms (Menu 4-1-2) and for
(Menu 4-1-3) or also as Sync Input / meter inputs (Menu
4-1-1 / Menu 4-1-6); see also chapter
SIOX - connection of energy, gas, water and event meters
System centre
The controller has 2 floating 230 V AC digital inputs (IN1: A1/A2 and IN2 - IN2: B1/B2); for details, see chapter
Terminal assignment of the digital inputs 230 V AC
SIOX extension module
By using up to a maximum of 4 SIOX extension modules (see chapter
SIOX - connection to the system centre
the number of inputs can be increased by another 48 digital inputs (12 digital inputs for each SIOX module, see
Menu 4-1-1), for see details see chapter
SIOX – Terminal assignment of the 230 V AC digital inputs
DANGER
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE
connecting and
disconnecting it must be checked
that
no voltage is present
at the 230 V AC digital inputs!
SIOX operating instructions
Comprehensive details on the SIOX extension modules and their current operating instructions can be
found here:
https://edp.eckelmann.de/edp/lds/_S88KwDvR7a