Firmware V7.16.x
16.05.2023
176/183
•
•
12 Specifications of System Centre and SIOX
12.1 Electrical data
System centre
Operating voltage
230 V AC, 200 - 265 V AC, 50 Hz
Rated power
36 W
Leakage current over PE
(protective earth)
max 1 mA
Digital inputs
1)
2 x 230 V AC floating output,
for external alarms (inputs IN.1 and IN.2)
Relay outputs
1)
3 x changeover contact for signalling system, floating output:
2 x 230 V AC, min. >= 10 mA, load type:
max. 6 A (ohmic) / max. 3 A (inductive) / (24 V DC / max. 5 A DC)
For outputs PRIO.1 and PRIO.2 with bistable relays and 5 minutes response delay after shutdown
of the device.
1 x 230 V AC min. 5 V / 10 mA max 230 V AC / 6 A max. 24 V DC / 5 A
For output AUX, e.g. for audible signalling unit
Manual control switch
-
Field bus interface
2 x CAN bus, floating output
Data ports
1x data port for SIOX
2 x Ethernet
1 x seriell RS485
3 x seriell RS232
2 x USB (Host/Slave)
Archive memory
Compressor run times, starts,
quotas, messages
Real-time clock
With power reserve and lithium cell (for details, see ""Transport and storage")
Accuracy: typical 12 minutes per year at 25 °C
Monitoring function
Watchdog
Other interfaces
Power supply for external SIOX
Environmental conditions
Transport and storage
The controller contains a 3 V lithium cell (design type CRC 2450 N, shelf life 10 years) with capacity of 540
mAh and lithium content of 0.16 g.
The battery complies with the UN3090 requirements for lithium metal cells. No special markings or
measures for transport and storage are required up to a lithium amount of 2.5 kg per package (total amount
for pallets or containers).
Weight
approx. 1600 g
Temperature range
Transport: -20 °C ... +80 °C
Operation: 0 °C ... +50 °C
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
Overvoltage category II / soiling degree 2:
All connections of the device provided for operation with
230 V AC supply voltage
must
be wired with the same phase conductor. 400 V AC between
neighbouring connection terminals is
not
permitted!