9.8 Menu 6 Configuration
CONFIGURAT POS: XXXXX
1 Refriger. Point
Move to menu 6-1
2 Controller
Move to menu 6-2
3 Language
Move to menu 6-3
•
Menu 6-1 Refriger. Point
REFR. PT. POS: XXXXX
Entry
Default
Refr. Pt. Name:
Text only
xxxxxxxxxxxxxxx
Free text entry describing refrigeration point (see note following table)
Case controller
Item ID: XXXXX
Free text entry displayed in screens after POS ID (see note following
table)
UA400
Priority: XX
Alarm priority in failure of refrigeration point
1
Sensor Fault XXX
Sensor break alarm delay
0..15
0m
No. Sensors XX
Number of temperature sensors connected. After entering
sensor
scan is performed to redetermine the number of sensors.
•
Menu 6-2 Controller
CONTROLLER POS: XXXXX
1 Type and Version
Move to menu 6-2-1
2 Sensor type
Move to menu 6-2-5
•
Menu 6-2-1 Type and Version
VERSION POS: XXXXX
Entry
Default
CTRLR. Type XXXXXXX Set by DIP switch S3
-
UA400L
Software Vers.: XXXX
Software version of case controller -
Serial No.: XXXXXX
Device No. of case controller
-
A meaningful name that describes the refrigeration point in more detail should be entered, e.g. Cheese
Counter 2 and CC2. The input is made using the menus of the system centre, store computer, operator
terminal or the BT 300 operator interface.