Firmware V3.00
05.08.2019
85/100
9.3 Menu 1 Actual Value
ACT VALUES POS: XXXXX
Temperat. Rx.y xxx°C
Temperature at sensor Rx.y
Cooling x ON/OFF
Cooling status, x=1 .. 5 (only shown for sensors Rx.1 to Rx.5)
Defrost x ON/OFF
Defrosting status, x=1 .. 5 (only shown for sensors Rx.1 to Rx.5)
Alarm x ON/OFF
Alarm status
Last Defrst dd hh:mm
Day and time of last defrost cycle started (only shown for sensors Rx.1 to Rx.5)
9.4 Menu 2 Setpoints
SETPOINTS POS:
XXXXX
Entry
Default
High Temp: xxx°C
High temperature setpoint
-50..100
10°C
Low Temp: xxx°C
Low temperature setpoint
-50..100
-5°C
Delay: xxm
High or low temperature delay
0..150
2m
Priority: xx
High or low temperature alarm priority
1)
↑, ↓, --, 0..2
–
Setpoint: xxx°C
Refrigeration point temperature setpoint (only shown for
sensors Rx.1 .. Rx.5)
-50..80
5°C
Hysteresis: xK
Refrigeration point hysteresis (only shown for sensors Rx.
1 .. Rx.5)
1..20
1K
Name:Temp. Rx.y
Name of sensor Rx.y (max. 10 characters)
Numbers
Rx.y
Pos.:Pos.y
Item ID of sensor Rx.y (max. 5 characters)
Numbers
Pos.y
Offset xK
Temperature sensor offset
-50..100
0K
Def. End. Tmp. xxx°C
Defrost termination temperature setpoint (only shown for
sensors Rx.1 .. Rx.5)
--, 5..20
12°C
EU Arch. CAN XX
CAN bus address of case/coldroom controller for which
temperature is to be recorded. No recording takes place
when set to "-".
--, 1..99
CAN bus address of
controller
EU Arch. Zone XX
Temperature zone of case/coldroom controller for which
temperature is to be recorded:1 to 2 Temperature zone of
case/coldroom controller 3 to 10 Temperature sensor (e.g.
another UA 410 L in the system)
1..10
1)
In the LDSWin (PC software) a sensor is recognized as used when its priority is set to 0, 1 or 2 and
is held to be not used (no message, alarm or recording), when set to "--".