Installation and Startup of UA 410 D
46
Firmware V1.40 - Doku 2.1 06. April 2016
5.6.1
Naming of the controller
The following parameters are available for naming the controller:
- refrigeration point name
(19 characters, can be freely edited)
- refrigeration point position
(5 characters, can be freely edited)
The controller can be named using the system centre, store computer, operator terminal or the PC software
LDSWin.
A. BT 300 operator interface
The input is made in Menu 6-1.
Eine Benennung des Reglers mit einem Bediengerät BT 300 x
ist nur beim Regler UA 410 L möglich!
B. System centre
See chapter 7.3.2.1 for details.
A. Store computer / operator terminal
The input is made in Menu 7-2.
D. PC software LDSWin
See operating manual of LDSWin.
5.7
Restart - restart of the controller
For a restart, the device is restarted with all configured parameters and the CAN bus address set on the rotary
switch. A restart can be initiated using the following procedure:
- disconnection and reconnection of the power supply
5.8
First start / reset controller to factory settings
Caution: data loss!
A first start causes all parameters to be reset to the factory settings!
All parameters are reset to the factory settings during a first start. This can be achieved by the following
procedure:
1. Disconnect controller from the power supply for safety reasons (see also chapter 5.4) and
make a note of the settings of the DIP switch S3 (e.g. B. OFF-ON-OFF-...).
2. Adjust settings at the DIP switch S3 (e.g. OFF-OFF-OFF-...).
3. Power off the controller for a short time.
4. Power on the controller again and wait approx. 1 minute while the controller starts up.
5. Disconnect controller from the power supply for safety reasons (see also chapter 5.4).
6. Reset DIP switch S3 to the noted starting position.
7. Switch on controller again.
8. The settings of the controller have been reset to the factory settings.
A first start is also performed when a different controller version (e. g UA 400
´
UA 410 D
´
UA 400
E
´
UA 410 L) is loaded on the controller via firmware update, see chapter 5.10.
A sensor scan (Menu 6-1) must be performed during commissioning or after any first start. The sen
sor scan is the only possibility to define the sensors to be monitored; see chapter 4.1.1.
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...