Firmware V3.15
21.04.2021
92/401
•
•
10.
Tap the
ESC
button twice to exit the menu
3 Toggle Setpoint
.
11.
Select menu
2 Setpoints - 1 Cooling - Zone 1 / Zone 2 / Zone 1U / Zone 2U
.
2 Setpoints - 1 Cooling - Zone 1 - 2 - Um1 - Um2
KÜHLUNG xPOS: XXX
...
Überhitzung XK
Superheat setpoint of the superheat controller
Min. Überh. XK
If the minimum superheat is undercut, the controller closes the associated E-
valve and sets the I-sum (NOT: I-component) to 0 if the parameter
Reset I-
Summ
is set to ON.
Zweipunktreg .AUS
The temperature control no longer operates continuously but as on-off
controller. This is used for enable / disable of the superheat control (TEV
emulation).
MOP-Punkt XX°C
A value not equal to "–" must be set here if the MOP function is required. If t0
exceeds this value, the opening degree is reduced as t0 rises.
12.
Return to the main menu of the store computer / operator terminal by tapping the
ESC
button multiple
times.
13.
Select the menu
7 Monitoring - 3 Configuration
in the main menu of the store computer / operator
terminal and input, among other things, the node name of the case controller in plain text.
7 Monitoring - 3 Configuration
KONFIGURATION Kn.nnn
Input of the CAN bus address: Select the case controller with the corresponding
CAN bus address (node No. = 1..99) to be parametrised using the cursor or by
direct input.
Teilnehmername
Input node name (e.g. Cheese Counter)
Position XXXXX
Input of the position of the node in the store
Priorität X
Input of the desired priority
14. Ending basic configuration of the controller
Tap the
ESC
button multiple times to return to the main
menu. This ends the basic configuration.
6.4.1 Naming of the controller
The following parameters are available for naming the controller:
Refrigeration point name (19 characters, can be freely edited)
Refrigeration point position (5 characters, can be freely edited)
The controller can be named using the system centre, store computer, operator terminal or the PC software
LDSWin.
A. BT 300 operator interface
the input is made in Menu 6-1.
B. System centre
See
chapter
A. Store computer / operator terminal
the input is made in Menu 7-2.
D. PC software LDSWin
See operating manual of LDSWin.
Any naming of the controller with a BT 300 x operator interface is only possible for the UA 410 L
controller.
Summary of Contents for UA 400
Page 26: ...Firmware V3 15 21 04 2021 26 401 Solenoid valve Relay for Solenoid Valve 1...
Page 172: ...Firmware V3 15 21 04 2021 172 401 Service Mode 6 7 2 SERVICE MOD...
Page 244: ...Firmware V3 15 21 04 2021 244 401...
Page 361: ...Firmware V3 15 21 04 2021 361 401 FANS 2 Pos XXXXX Fan Delay Fan delay...
Page 372: ...Firmware V3 15 21 04 2021 372 401...