Firmware: V2.18 / V--
26.10.2022
17/119
•
•
•
3.2.1 Number of data points
A maximum of 4 controllers of the type GLT x010 can be used system-wide in the E*LDS system.
GLT 3010:
The system centre can manage a total of
600 data points
system-wide (150 per controller) and archive a
maximum of
255
data points.
GLT 5010:
The system centre can manage a total of
2000 data points
system-wide (500 per controller) and archive a
maximum of
1020
data points (255 per controller).
3.2.2 Synchronisation
In this chapter, the aspects of synchronisation of the GLT channel configurations of the GLT 5010 and the
system centre will be covered.
Synchronisation from the perspective of the system centre
In the case of a first start or a restart of the system centre, the system centre will query the GLT channel
configuration of all existing GLT 5010 controllers in the field and persist if necessary.
Synchronisation from the perspective of the GLT 5010
In the case of a restart of the GLT 5010 or a change in the GLT channel configuration in the GLT 5010, the GLT
5010 sends its GLT channel configuration to the system centre automatically.
3.2.3 Compatibility
The new functionality is already integrated in the Virtus 5 series and GLT 5010. A suitable
supports the necessary functionalities is required for this. A system centre in the
converted into an equivalent system centre in the
by purchasing an upgrade.
New installation
Due to the larger data volumes, the Virtus 5 series will no longer support the
("
Netporty
") in the future.
In the case of new installations with a system centre in the CI 5000 series, GLT 5010 controllers
must
be used in order to be able to use the concept with the separate GLT configurations.