Firmware: V2.18 / V--
26.10.2022
103/119
10.3.2 Assignment of the analogue outputs
Analogue outputs (AO1..4)
AO
Terminal No.
I/O
No.
Address
process image
Assignment
at the factory
Function
53
54
1
QW28
0..10 V
GND
Freely programmable
55
56
2
QW29
0..10 V
GND
57
58
3
QW30
0..10 V
GND
63
64
4
QW31
0..10 V
GND
Configuration of the analogue inputs and outputs
DANGER
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
If supply
voltage is connected to the analogue outputs, there is a risk of personal injury as the analogue outputs
are not galvanically isolated from other system components (e.g. pressure transmitters). Furthermore
this will destroy the controller!
ATTENTION
Malfunction due to interference!
All supply lines from and to the controller (with the exception of the
230 V power supply and signal lines) must be shielded (cable type LiYCY)! This particularly applies for
the analogue inputs and outputs (e.g. sensor supply lines). As a general rule, care should be taken to
ensure that signal cables and cables carrying mains voltage are routed in separate cable channels