Installation and Startup of Combi Gateway
39
Version 1.6 04. November 2016
6.6.6
Setup of the COM Port Server
The COM Port Server software module is integrated in the Combi Gateway as standard. The TCP port and baud
rate parameters can be configured on the
COM Port Server
tab for the correct functioning.
It is recommended to use the value 38400 (default) as baud rate.
6.6.6.1 Connection to a GLT 3010
The COM port (RJ45 interface "RS232") of the Combi Gateway must be connected to the COM port of the re
spective controller. The cable set with the part number KABCOMSRV1 is needed for this, see chapter 7.1.4.
6.6.6.2 Required software on the user PC
An additional program (not included in the scope of delivery) is needed on the PC to connect to a GLT 3010
using CoDeSys via the "COM Port Server" function. This program emulates a local COM port on the PC and
connects this to the Combi Gateway via the network.
Basically any program that transfers serial data in the "RAW" mode can be used for this.
Serial Port Redirector from Fabulatech has been tested and is recommended:
http://www.fabulatech.com/serial-port-redirector.html
See its own documentation for operation of the "Serial Port Redirector".
The required parameters for a successful connection are:
- IP address of the Combi Gateway, see chapter 6.5
- Port of the COM Port Server (default: 1041)
- Protocol "RAW"
Summary of Contents for Combi
Page 1: ...Version 1 6 04 November 2016 Operating instruction Combi Gateway Version V1 57 ...
Page 6: ...iv Version 1 6 04 November 2016 Notice ...
Page 18: ...Application Combi Gateway 12 Version 1 6 04 November 2016 Notice ...
Page 54: ...Decommissioning and disposal 48 Version 1 6 04 November 2016 Notice ...
Page 58: ...Order No s and accessories 52 Version 1 6 04 November 2016 Notice ...