Firmware V3.13
21.04.2021
88/466
•
•
•
•
switching on and off during a defrost in two-zone operation. In single-zone mode only defrost sensor R1.1
controls the fan relay.
R1.1: Defrost sensor (Terminal Z31/Z32)
Expansion valve 1: Expansion valve 1 (Terminal 23/24)
Fan 1: Fan control relay (Terminal 73/74)
When thermal fan start delay is set, the fan does not start for a time after defrosting is terminated so as to
prevent warm air being forced into the display case.
The fan relay is the inverted type:
when the controller turns on the fan, then the relay contact (73/73) is opened;
when the controller turns off the fan then the relay contact (73/73) is closed.
5.10.3 Fan control - controller type UA 131 E LS with enhanced fan control
The enhanced functions for the fan control must be activated via the DIP switch S3 on the circuit board of the
case controller.
Apart from the terminal assignment of the analogue inputs for temperature sensors, the terminal assignment is
identical to the terminal assignment of the UA 131 E, see chapter
Belegung der Analogeingänge für
The fan relay operates inverted:
if the controller switches on the fan, the relay contact (73/74) is opened;
if the controller switches off the fan, the relay contact (73/74) is closed.
Version 1.10:
If the Fan Delay parameter is set to ”--”, the fan will remain continuously off.
From Version 1.11:
If the Fan Delay parameter is set to ”--”, the fan will remain continuously on.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...