Firmware V3.13
21.04.2021
118/466
6 Installation and Startup of UA 4xx E
6.1 Installation
The case/coldroom controller is produced in the types UA 401 E CC / UA 401 E CC / UA 410 E AC.
6.1.1 DIN rail mounting of the controller for electronic valves
The case controller is attached to the DIN rail (35 mm) using two retaining springs. The DIN rail must have
a minimum height of 5 mm.
UA 410 E AC - fill configuration
Electrical enclosure and dimensions are listed in Section
DANGER
Important safety instructions!
Before the installation and commissioning of the controller, chapter
should be carefully read in its entirety and all safety instructions and hazard
warnings observed.
The controller should only be used with compatible versions of the PC software LDSWin, otherwise the
range of functions could be restricted.
Tip:
should be used at all times.
Further details on the distinguishing features of the controllers types are contained in chapter
ATTENTION
The case controller may only be mounted on a Cap (DIN) rail and operated as an integrated regulation
and control device (EN60730). Power loss of the controller is approx. 11 VA, which needs to be taken
into account when installing the unit.
All leads running to and from the case controller - especially those of the CAN bus - must be shielded
(cable type: LiYCY)! No shielding is required on sensor leads when installed exclusively
inside the refrigerated display case and when external interference (for example from parallel power
wires) is not to be expected (see operating instruction “
Grundlagen und allgemeine Sicherheits- und
”). As a general rule, care should be taken to ensure that signal leads and leads
carrying a supply voltage are routed through separate cable channels.
Summary of Contents for Case Controller UA 4 E Series
Page 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E...
Page 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice...
Page 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller...
Page 207: ...Firmware V3 13 21 04 2021 207 466...
Page 277: ...Firmware V3 13 21 04 2021 277 466...