All optical fibers should be arranged in groups inside
the FST, and fastened with Velcro strips.
7.
Run the fibers up to the level of the corresponding optical connector.
8.
Return the FST to the rack until it latches in place with a click.
C
AUTION
:
Make sure that all the optical connectors are
closed at all times with the appropriate protective caps or with
the mating cable connector. Do not remove the protective cap
until an optical fiber is connected to the corresponding
connector, and immediately install a protective cap after a
cable is disconnected.
The minimum bending radius of optical fibers is 35 mm.
Sharp bending of fibers may degrade the optical transmission
characteristics.
Installing the ODF
Identify the prescribed ODF locations in the rack before performing the
following procedures.
The ODF is supplied with two sets of rack mount brackets: one for 19 in. and
ETSI racks, and the other for 23 in. 7 foot bay racks. The 19 in./ETSI rack
mount brackets can be used for both ETSI A and ETSI B racks.
To attach the rack mount brackets to the ODF:
1.
Refer to the following figure to identify the required set of rack mount
brackets.