Before You Start
XDM-300 Installation and
Maintenance Manual
2-4 ECI
Telecom
Ltd.
Proprietary
417006-2311-0H3-A00
Site Preparation
Perform a preliminary survey of the installation site, taking into consideration
the following issues:
|
System environmental requirements
|
Physical location of the XDM-300 shelves
|
Location of power sources
|
Types of interfaces used at the site (optical, electrical, management, alarm
monitoring, and so on)
|
Work and equipment safety requirements
Environmental Requirements
The following environmental conditions must be provided at the installation
site:
Parameter Compliance
requirements
Electromagnetic interference
FTZ 1TR9, EN 55022/94, EN 50082-1/92
Temperature
ETSI ETS 300-19-2-3 Test Spec. T3.1
Physical Location
W
ARNING
:
XDM-300 shelves are intended for installation
in restricted access areas only.
Choose the physical location of the XDM-300 shelves, taking the following
aspects into consideration:
1.
Equipment dimensions, as specified in the following table.
2.
Required floor loading capability: 150 kg per rack for a typical 4-shelf
installation.
3.
Routing requirements for grounding, power, alarm monitoring, and
management cables, and optical fibers. To ensure convenient access to
cables and fibers, it is recommended to use overhead cable ladders
whenever possible, to bring the cables/fibers to the top of each rack.