ECI MOVFR-LCD Installation Manual
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
P a g e
|
23
▪
When fully OPEN the SPEED and MOTOR reading should go to 0 even with the
switch in OPEN position.
o
NOTE
that the HOLDING LED will not light as the OP HOLD SP and TORQ settings
are at default 0 settings.
o
Go to EDIT PARAMETERS screen and change OP hold torq and OP hold sp to 1.
NOTE:
these settings will have to be set >1 to ensure enough force to hold doors.
NOTE:
HOLDING power should not exceed 15W to prevent
motor
heating motor which
can reduce its life.
o
The HOLDING LED should light at the next open cycle.
•
Repeat with the CLOSE/OPEN switch in the CLOSE position.
o
NOTE
that the HOLDING LED will not light with DCL due to the CL HOLD SP and
TORQ settings are at default 0.
o
Go to EDIT PARAMETERS screen and change CL hold torq and CL hold sp to 1.
NOTE:
these settings will have to be set >1 to ensure enough force to hold doors.
NOTE:
HOLDING power should not exceed 15W to prevent
heating motor which can
reduce its life.
o
The HOLDING LED should light on the next close cycle.
8
Adjustments
At this time adjustments can be made through the parameter settings to produce smooth door
operation and adjust OPEN and CLOSE torque settings. Refer to section 8.1 for speed profiles and
CAM settings.
NOTE -
For HEAVY DOOR adjustments the elevator car must be at a “heavy door” floor. When
moving a heavy door in MAN operation the HEAVY switch must be used with the CLOSE and
OPEN switches.
NOTE: IT IS IMPORTANT TO RETURN THE DISPLAY TO THE MAIN MENU
WHEN ADJUSTMENTS ARE COMPLETE. FAILING TO DO SO WILL RESULT
IN PARAMETERS REVERTING TO DEFAULT SETTINGS SHOULD POWER
BE LOST.