Automatic Transfer Switch - VERSO 200 - Attachment 2 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-

 

Press OK,

 

2-

 

Press 

 Until you reach menu: 

PARAM

 (to modify a parameter), and press OK

TIMER

 (to modify a timer), and press OK

3-

 

Press OK,

 

4-

 

Press 

 or 

 until you reach the desired parameter or timer,

 

5-

 

Press OK to access the parameter or timer,

 

6-

 

Press 

 or 

 to modify the parameter or timer,

 

7-

 

Press OK to accept the modification,

 

8-

 

Press 

 twice to exit the menu. 

See list of timers and parameters overleaf 

A21 

Modification of parameters/timers 

 

 

 

Three inputs IN1 (terminals 1 & 2, connection J6), IN2 (terminals 3 & 4), IN3 (terminals 5 & 6, connection J6

Table of programmable functions (F01 to F08F00 = no function) 

 

F01  PreavisEJP  Notice of EJP 

(*STOR)

  F04  (2) >0KW  Request production 

F07  1->(0)<-2  Set to position 0 

F02  Top EJP  TOP EJP 

(*STOR)

 

F05  (2) >0KW+T  Request timed production 

F08  Lamp test  LED and screen test 

F03  Prior EJP  EJP priority 

F06  (1) =OK ?  Confirmation of sector return  F09 

SOS 4F01  Trip 

lightning conductor

 reporting  

  

Two outputs OUT1 (terminals 2 & 3, connection J13), OUT2 (terminals 2 & 3, connection J14

Table of programmable functions (F01 to F12F00 = no function) 

 

F01 

-> (1) 

Opening of source 1 

F05 

(1) OK 

source 1 OK 

F09 

EJP 

EJP mode 

(French market only)

  

F02 

-> (2) 

Opening of source 2 

F06 

(2) OK 

source 2 OK 

F10 

=IN#1  Input 1 reporting 

F03 

(1) -> 

Closure of source 1 

F07  (AUTO NOK  mode AUTO not OK 

F11 

=IN#2  Input 2 reporting 

F04 

(2) -> 

Closure of source 2 

F08 

(2) + T22 

Request load shedding 

F12 

=IN#3  Input 3 reporting 

 

Programming inputs and outputs 

1-

 

Press OK,

 

2-

 

Press 

 until you reach menu 

I/O,

 

3-

 

Press OK,

 

4-

 

In the 

Input/Output

 menu,

 

press 

 or 

 until you reach;

 

- the desired input (IN#1IN#2 or IN#3), 

- the desired output (OUT1#1 or OUT#2),  

5-

 

Press OK to access the programming:

 

- of the input selected (IN#1IN#2 or IN#3), 

- of the output selected (OUT#1 or OUT#2), 

6-

 Select the desired function by pressing 

 or 

,

  

7-

 

Press OK to validate the function,

 

8-

 

Press 

 twice to exit the menu. 

 

 

 

 

 

 

Programming inputs and outputs 

A22 

Example of programming of 

three inputs 

Example of programming of 

two outputs 

 

 

 

 

1-

 

Press OK

2-

 

Press 

 until you reach the 

PROGRAMS 

menu,

 

3-

 

Press OK,

 

4-

 

In the 

PROGRAMS 

menu, select Program1Program2 or Program3 by pressing 

 or 

,

 

5-

 

Press OK to access the chosen program selection, the message Off will be flashing (see above),  

6-

 Each program has two criteria: Period = Off1DayDays or Week (see table) and Test = 0KW or >0KW

 

option  inactive  date 

 

 

start 

 

stop 

365 

 

52 

Off 

 

 

 

 

 

1Day 

 

 

 

Days 

 

 

x   

Week 

 

  x 

Test = 0KW = test without load 

Test = >0KW = test with load 

365 = everyday, 52 = every week 

 

 

 

Setting the clock 

A23 

1Day program 

Days program 

Week program 

*STOR=

 

Short Term Operating Reserve

 

Summary of Contents for VERSO200

Page 1: ... et de fonctionnement Operating instruction manual Manual descriptivo y de funcionamiento SDMO Inverseur de sources automatique Automatic transfer switch Inversor de fuentes automático VERSO200 02 08 2013 33514066401_0_1 ...

Page 2: ... switch This applies to both the mains side and the generating set side Read carefully the information provided on the electrical drawing Preliminary checks 3 The electrical box has four 7mm diameter holes for wall mounting or affixing to a suitable metallic bracket Only use suitable professional materials for the mounting bracket The template for mounting the box is shown on the packaging The box...

Page 3: ...monitoring fault source 1 4 Source 2 switch open Source 2 switch closed Position monitoring fault source 2 5 No force switch to source 1 Force switch to source 1 selected 6 No force switch to source 2 Force switch to source 2 selected 7 AUTO mode not selected AUTO mode selected 8 TEST mode not selected TEST mode selected Diagnostics LED functions 8 4 key navigation keypad 9 Access to previous menu...

Page 4: ... genset circuit breaker check voltage and phase sequence If phase rotation is not correct LED 12 turns red open the genset breaker and restore phase sequence Commissioning 10 Source 1 present and parameters are correct Frequency source 2 Voltages phase to neutral of type 3P N Phase voltage between phases of type 3P N Electrical measurements display 11 Displays may be different depending on type of...

Page 5: ...on at source 1 2 AUTOSET OK auto configuration initialising MODE EJP EJP STOR mode engaged France only AUTOSET auto configuration in progress flashing PROGRAM Program inprogress DEL test switchedon On the third and fourth lines the following action messages may be displayed T00 003s 1 0 Transfer Timer 1 OK CONFIRM _____CONFIRM OK Manual confirmation of return to mains T01 005s 2 1 Return to mains ...

Page 6: ...ers A11 N function Range of adjustment Standard range N function Range of adjustment Std settings T00 Loss of source 1 0s to 180s 3 T26 Screen scrolling time 1s to 10s 5 T01 Return source 2 0s to 999s 5 T27 Automatic configuration 0s to 999s 3 T02 min U source 1 0s to 999s 5 T28 Min critical U source 1 0s to 999s 1 T03 max U source 1 0s to 999s 5 T29 Max critical U source 1 0s to 999s 1 T04 min U ...

Page 7: ...ening of source 2 F06 2 OK source 2 OK F10 IN 1 Input 1 reporting F03 1 Closure of source 1 F07 AUTO NOK mode AUTO not OK F11 IN 2 Input 2 reporting F04 2 Closure of source 2 F08 2 T22 Request load shedding F12 IN 3 Input 3 reporting Programming inputs and outputs 1 Press OK 2 Press until you reach menu I O 3 Press OK 4 In the Input Output menu press or until you reach the desired input IN 1 IN 2 ...