Automatic Transfer Switch - VERSO 200 - Attachment 1 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

designation 

function 

Possible values 

Std settings 

Type 

Mains 

3P+N3P2P+N1P+N 

AUTOCONF 

Unom 

Voltage in Volts 

440415400380240230220208 

AUTOCONF 

Fnom 

Frequency in Hz 

50Hz60Hz 

AUTOCONF 

(1)

_

U<% 

Default min mains U threshold 

Range of adjustment dependant on apparatus  

15 

(2)

_

U<% 

Default min genset U threshold 

Range of adjustment dependant on apparatus 

15 

(1)

_

U>% 

Default max mains U threshold 

Range of adjustment dependant on apparatus 

10 

(2)

_

U>% 

Default max genset U threshold 

Range of adjustment dependant on apparatus 

10 

(1)

_

Hz<% 

Default min mains F threshold 

Range of adjustment dependant on apparatus 

(2)

_

Hz<% 

Default min genset F threshold 

Range of adjustment dependant on apparatus 

(1)

_

Hz>% 

Default max mains F threshold 

Range of adjustment dependant on apparatus 

(2)

_

Hz>% 

Default max genset F threshold 

Range of adjustment dependant on apparatus 

ABC 

Direction of phase rotation 

ABCACBOFF (no management) 

ABC 

(1)

_

V/V 

Adjustment of mains voltage measuring 

Voltage gain adjustment (1=0,1V) (e.g.: ) 

1000 

(2)

_

V/V 

Adjustment of genset voltage measuring 

Voltage gain adjustment (1=0,1V) (e.g.:) 

1000 

Position 

Management of returns positions 

YES=management, NO=no management 

YES 

Bklight 

LCD screen backlight 

 

99 

Contrast 

LCD screen contrast 

 

50 

Modbus 

Modbus card 

YES=with Modbus, NO=without Modbus 

NO 

Prio EJP 

Default priority to EJP (*STOR) 

(France only)

  YES=application, NO=no application 

NO 

(1)

_

OK? 

Manual confirmation of return to mains 

YES=confirmation required, NO=confirmation not required 

NO 

NO % 

No management of U and F limits 

OFF=operation with limits, ON=operation without limits 

OFF 

Hyst/U% 

Hysteresis U value 

between 0% and 3% (of voltage limit) 

Hyst/F% 

Hysteresis F value 

between 0% and 2% (of frequency limit) 

(1)

_

+/- 

Measuring card adjustment 

Adjustment of offset voltage of measuring card 5A07 

100 

 

List of parameters 

A11 

 

 

 

N° 

function 

Range of 

adjustment 

Standard 

range 

  N° 

function 

Range of 

adjustment 

Std 

settings 

T00  Loss of source 1 

0s to 180

  T26  Screen scrolling time 

1s to 10

T01  Return source 2 

0s to 999

  T27  Automatic configuration 

0s to 999s

 

T02  min U source 1 

0s to 999

  T28  Min critical U source 1 

0s to 999s

 

T03  max U source 1 

0s to 999

  T29  Max critical U source 1 

0s to 999s

 

T04  min U source 2 

0s to 999

  T30  min critical U source 2 

0s to 999s

 

T05  max U source 2 

0s to 999

  T31  max critical U source 2 

0s to 999s

 

T06  min F source 1 

0s to 999

  T32  min critical F source 1 

0s to 999s

 

T07  max F source 1 

0s to 999

  T33  max critical F source 1 

0s to 999s

 

T08  min F source 2 

0s to 999

  T34  min critical F source 2 

0s to 999s

 

T09  max F source 2 

0s to 999

  T35  max critical F source 2 

0s to 999s

 

T10  default command source 1  

2s to 999

  T36  last fault source 1 

0s/10 to 999s/10

 

T11  default command source 2 

2s to 999

  T37  reserve 

0s to 999s

 

T12  Source change over 

0s/10 to 999s/10 

10 

  T38  last fault source 2 

0s/10 to 999s/10

 

T13  U stabilisation source 1 

0s/10 to 999s/10

 

10 

  T39  reserve 

0s to 999s

 

T14  U stabilisation source 2 

0s/10 to 999s/10

 

30 

  T40  production demand 

0s to 999s

 

10 

T15  U setting source 1 

0s/10 to 999s/10

 

  T41  switch power supply 

0s to 999s

 

T16  U setting source 2 

0s/10 to 999s/10

 

  T42  activate back-light 

0s to 999s

 

15 

T17  Genset cooling source 1 

0s to 999s

 

60 

  T43  Default opening at source 1 

0s to 999s

 

T18  Genset cooling source 2 

0s to 999s

 

60 

  T44  Default opening at source 2 

0s to 999s

 

T19  test 

0s to 999s

 

600 

  T45  reserve 

0s to 999s

 

T20  advance warning EJP (*STOR)  0min to 999min 

20 

  T46  reserve 

0s to 999s

 

T21  loss EJP (*STOR) 

0s to 999s

 

600 

  T47  reserve 

0s to 999s

 

T22  load shedding 

0s to 999s

 

10 

  T48  reserve 

0s to 999s

 

T23  non-start 

0s to 999s

 

30 

  T49  reserve 

0s to 999s

 

T24  return to home screen 

0s to 999s

 

120 

   

 

 

 

T25  Standby 

0s to 999s

 

120 

   

 

 

 

s=second      min=minute      s/10= tenth of a second      U=voltage      F=frequency 

*STOR=

 

Short Term Operating Reserve

 

List of timers 

A12 

Summary of Contents for VERSO200

Page 1: ... et de fonctionnement Operating instruction manual Manual descriptivo y de funcionamiento SDMO Inverseur de sources automatique Automatic transfer switch Inversor de fuentes automático VERSO200 02 08 2013 33514066401_0_1 ...

Page 2: ... switch This applies to both the mains side and the generating set side Read carefully the information provided on the electrical drawing Preliminary checks 3 The electrical box has four 7mm diameter holes for wall mounting or affixing to a suitable metallic bracket Only use suitable professional materials for the mounting bracket The template for mounting the box is shown on the packaging The box...

Page 3: ...monitoring fault source 1 4 Source 2 switch open Source 2 switch closed Position monitoring fault source 2 5 No force switch to source 1 Force switch to source 1 selected 6 No force switch to source 2 Force switch to source 2 selected 7 AUTO mode not selected AUTO mode selected 8 TEST mode not selected TEST mode selected Diagnostics LED functions 8 4 key navigation keypad 9 Access to previous menu...

Page 4: ... genset circuit breaker check voltage and phase sequence If phase rotation is not correct LED 12 turns red open the genset breaker and restore phase sequence Commissioning 10 Source 1 present and parameters are correct Frequency source 2 Voltages phase to neutral of type 3P N Phase voltage between phases of type 3P N Electrical measurements display 11 Displays may be different depending on type of...

Page 5: ...on at source 1 2 AUTOSET OK auto configuration initialising MODE EJP EJP STOR mode engaged France only AUTOSET auto configuration in progress flashing PROGRAM Program inprogress DEL test switchedon On the third and fourth lines the following action messages may be displayed T00 003s 1 0 Transfer Timer 1 OK CONFIRM _____CONFIRM OK Manual confirmation of return to mains T01 005s 2 1 Return to mains ...

Page 6: ...ers A11 N function Range of adjustment Standard range N function Range of adjustment Std settings T00 Loss of source 1 0s to 180s 3 T26 Screen scrolling time 1s to 10s 5 T01 Return source 2 0s to 999s 5 T27 Automatic configuration 0s to 999s 3 T02 min U source 1 0s to 999s 5 T28 Min critical U source 1 0s to 999s 1 T03 max U source 1 0s to 999s 5 T29 Max critical U source 1 0s to 999s 1 T04 min U ...

Page 7: ...ening of source 2 F06 2 OK source 2 OK F10 IN 1 Input 1 reporting F03 1 Closure of source 1 F07 AUTO NOK mode AUTO not OK F11 IN 2 Input 2 reporting F04 2 Closure of source 2 F08 2 T22 Request load shedding F12 IN 3 Input 3 reporting Programming inputs and outputs 1 Press OK 2 Press until you reach menu I O 3 Press OK 4 In the Input Output menu press or until you reach the desired input IN 1 IN 2 ...