Information, reports, alarms and faults are displayed as coded messages. 

 

On the first line only the following messages may be displayed: 

 (1) OK 

source 1 operational 

(2) OK 

source 2 operational 

(1) ??? 

source 1 detected but configuration incompatible 

(2) ??? 

source 1 detected but configuration incompatible 

(1) U<% 

Under-voltage alarm or fault at source 1 

(2) U<% 

Under-voltage alarm or fault at source 2 

(1) U>% 

Over-voltage alarm or fault at source 1 

(2) U>% 

Over-voltage alarm or fault at source 2 

(1) F<% 

Under-frequency alarm or fault at source 1 

(2) F<% 

Under-frequency alarm or fault at source 2 

(1) F>% 

Over-frequency alarm or fault at source 1 

(2) F>% 

Over-frequency alarm or fault at source 2 

(1) ACB 

Phase rotation fault at source 1 

(2) ACB 

Phase rotation fault at source 2 

  

On the third line only the following messages may be displayed: 

(0) -> (1) =SOS 

Failure to close at source 1 

(0) -> (2) =SOS 

Failure to close at source 2 

(1) -> (0) =SOS 

Failure to open at source 1 

(2) -> (0) =SOS 

Failure to open at source 2 

(1) =SOS ACB 

Phase sequence fault at source 1 

(2) =SOS ACB 

Phase sequence fault at source 2 

 

 

(2) =SOS GEN START 

Genset fail to start 

note

: With regards to the messages mentioned in this table, the fourth line will display the message RESET = 

OK meaning « Press OK » to reset the fault 

 

On the third line only the following action messages may be displayed: 

ATS = 0 

Opening function at source 1 & 2 

AUTOSET  =OK 

auto-configuration initialising 

MODE EJP 

EJP (STOR*) mode engaged 

(France only)

 

|--AUTOSET--| 

auto-configuration in progress 

(flashing)

 

PROGRAM 

Program in progress 

(+ DEL “test” switched on)

 

 

 

 

On the third and fourth lines the following action messages may be displayed: 

T00=003s 

(1) -> (0) 

Transfer Timer 

(1) =OK CONFIRM ? 

_____

CONFIRM=OK 

Manual confirmation of return to 

mains

 

T01=005s 

(2) -> (1) 

Return to mains timer 

T19=600s 

MODE TEST 

Test mode ongoing 

T17=060s 

(1) <°C 

Genset cooling timer 

(source 1) 

(not implemented)

 

T18=060s 

(2) <°C 

Genset cooling timer 

(source 2)

 

T20=020min 

Préavis EJP 

Advance notice of EJP (STOR*) timer 

Short Term Operating Reserve

 

T21=600min 

Perte EJP 

loss of EJP (STOR*) timer 

*Short Term Operating Reserve 

 
 

 

 

Pressing TEST will light up LED [8], start up the generating set and make the screen displayed below appear. 

Two possible modes: 

- test with load (TEST>0KW=OK), press OK to select this mode, 

- test without load (TEST 0KW=EXIT), press 

 to select this mode. 

The user will have a period of 30 seconds to make a selection. 

If no action is taken by the user, ‘TEST without load’ mode is selected automatically. 

Displays: Information, alarms, faults and statuses

 

13 

TEST mode 

14 

 

 

 

1-

 Press OK for access to various menus, 

2-

 Press OK to access 

LAMPS TEST menu

,  

3-

 Press OK. All LED’s and entire screen will light up. 

 

 

 

 

 

 

1-

 

Press OK,

 

2-

 

Press 

 until you reach 

STATS

,

 

3-

 

Press OK to access

 

4-

 

Press 

, to access   

 

Lamps test 

15 

STATS menu 

16 

 

 

 

1-

 

Press OK,

 

2-

 

Press 

 until you reach 

EVENTS

,

 

3-

 

Press OK,

 

4-

 

Press 

 or 

, to access the time-stamped list

 

 

 

EVENTS menu 

17 

Summary of Contents for VERSO200

Page 1: ... et de fonctionnement Operating instruction manual Manual descriptivo y de funcionamiento SDMO Inverseur de sources automatique Automatic transfer switch Inversor de fuentes automático VERSO200 02 08 2013 33514066401_0_1 ...

Page 2: ... switch This applies to both the mains side and the generating set side Read carefully the information provided on the electrical drawing Preliminary checks 3 The electrical box has four 7mm diameter holes for wall mounting or affixing to a suitable metallic bracket Only use suitable professional materials for the mounting bracket The template for mounting the box is shown on the packaging The box...

Page 3: ...monitoring fault source 1 4 Source 2 switch open Source 2 switch closed Position monitoring fault source 2 5 No force switch to source 1 Force switch to source 1 selected 6 No force switch to source 2 Force switch to source 2 selected 7 AUTO mode not selected AUTO mode selected 8 TEST mode not selected TEST mode selected Diagnostics LED functions 8 4 key navigation keypad 9 Access to previous menu...

Page 4: ... genset circuit breaker check voltage and phase sequence If phase rotation is not correct LED 12 turns red open the genset breaker and restore phase sequence Commissioning 10 Source 1 present and parameters are correct Frequency source 2 Voltages phase to neutral of type 3P N Phase voltage between phases of type 3P N Electrical measurements display 11 Displays may be different depending on type of...

Page 5: ...on at source 1 2 AUTOSET OK auto configuration initialising MODE EJP EJP STOR mode engaged France only AUTOSET auto configuration in progress flashing PROGRAM Program inprogress DEL test switchedon On the third and fourth lines the following action messages may be displayed T00 003s 1 0 Transfer Timer 1 OK CONFIRM _____CONFIRM OK Manual confirmation of return to mains T01 005s 2 1 Return to mains ...

Page 6: ...ers A11 N function Range of adjustment Standard range N function Range of adjustment Std settings T00 Loss of source 1 0s to 180s 3 T26 Screen scrolling time 1s to 10s 5 T01 Return source 2 0s to 999s 5 T27 Automatic configuration 0s to 999s 3 T02 min U source 1 0s to 999s 5 T28 Min critical U source 1 0s to 999s 1 T03 max U source 1 0s to 999s 5 T29 Max critical U source 1 0s to 999s 1 T04 min U ...

Page 7: ...ening of source 2 F06 2 OK source 2 OK F10 IN 1 Input 1 reporting F03 1 Closure of source 1 F07 AUTO NOK mode AUTO not OK F11 IN 2 Input 2 reporting F04 2 Closure of source 2 F08 2 T22 Request load shedding F12 IN 3 Input 3 reporting Programming inputs and outputs 1 Press OK 2 Press until you reach menu I O 3 Press OK 4 In the Input Output menu press or until you reach the desired input IN 1 IN 2 ...

Reviews: