Page 71
Model T80
S80 Serial Number (hi word)
Unit Serial Number (32 bit integer hi word)
2
32 bit
Long
Integer
R
54
36
S80 Serial Number (lo word)
Unit Serial Number (32 bit integer lo word)
55
37
S80 Fault Status
1
16 bit
Integer
R
56
38
S80 Sensor Type
Specific S80 sensor type (see S80 Sensor Types tab)
1
16 bit
Integer
R
57
39
S80 Sensor Chemical Type
Specific chemicals the S80 is set to detect (see S80
Sensor Types tab)
1
16 bit
Integer
RW
Y
58
3A
S80 Max Range (hi word)
Max sensor range (bytes 3 and 2)
2
32 bit
Floating
Point
R
59
3B
S80 Max Range (lo word)
Max sensor range (bytes 1 and 0)
60
3C
S80 Min Range (hi word)
Min sensor range (bytes 3 and 2)
2
32 bit
Floating
Point
R
61
3D
S80 Min Range (lo word)
Min sensor range (bytes 1 and 0)
62
3E
S80 Sensor Value (hi word)
Current sensor value (bytes 3 and 2)
2
32 bit
Floating
Point
R
63
3F
S80 Sensor Value (lo word)
Current sensor value (bytes 1 and 0)
64
40
S80 Sensor Voltage (hi
word)
Corresponding sensor voltage to the sensor value
(byte 3 and byte 2)
2
32 bit
Floating
Point
R
65
41
S80 Sensor Voltage (lo
word)
Corresponding sensor voltage to the sensor value
(byte 1 and byte 0)
66
42
S80 Sensor Temperature (hi
word)
Sensor Temperature (bytes 3 and 2)
2
32 bit
Floating
Point
R
67
43
S80 Sensor Temperature (lo
word)
Sensor Temperature (bytes 1 and 0)
68
44
S80 Sensor is a Sentinel
Sensor is a Sentinel Type (0 - No, 1 - Yes)
1
16 bit
Integer
R
69
45
S80 Sentinel Life %
% of Sensor life remaining
1
16 bit
Integer
R
70
46
S80 Sentinel Vs (hi word)
Scaled Sentinel Voltage (in mV) normalized to Vo
(bytes 3 and 2)
2
32 bit
Floating
Point
R
71
47
S80 Sentinel Vs (lo word)
Scaled Sentinel Voltage (in mV) normalized to Vo
(bytes 1 and 0)
72
48
S80 Sentinel Vo (hi word)
Sentinel 100% value (in mV) on the life relative to 0V
(bytes 3 and 2)
2
32 bit
Floating
Point
RW
Y
73
49
S80 Sentinel Vo (lo word)
Sentinel 100% value (in mV) on the life relative to 0V
(bytes 1 and 0)
74
4A
S80 Sentinel Range (hi word)
Sentinel Range (bytes 3 and 2)
2
32 bit
Floating
Point
RW
Y
75
4B
S80 Sentinel Range (lo word)
Sentinel Range (bytes 1 and 0)
76
4C
Sensor Full Name (18
characters max)
ASCII character bytes 0 and 1, ex. "AB" A - 65 (41
hexidecimal), B - 66 (42 hex), send 6566 (4142 hex).
The characters permitted are space ' ' (32 base 10, 20
hex) through '}' 125 base 10, 7D hex).
1
16 bit
Integer
RW
Y
77
4D
Sensor Full Name
ASCII bytes 2 and 3
1
16 bit
Integer
RW
Y
78
4E
Sensor Full Name
ASCII bytes 4 and 5
1
16 bit
Integer
RW
Y
79
4F
Sensor Full Name
ASCII bytes 6 and 7
1
16 bit
Integer
RW
Y
80
50
Sensor Full Name
ASCII bytes 8 and 9
1
16 bit
Integer
RW
Y
81
51
Sensor Full Name
ASCII bytes 10 and 11
1
16 bit
Integer
RW
Y
82
52
Sensor Full Name
ASCII bytes 12 and 13
1
16 bit
Integer
RW
Y
83
53
Sensor Full Name
ASCII bytes 14 and 15
1
16 bit
Integer
RW
Y
84
54
Sensor Full Name
ASCII bytes 16 and 17
1
16 bit
Integer
RW
Y
85
Sensor Abbreviated Name (8
characters max)
ASCII character bytes 0 and 1, ex. "AB" A - 65 (41
hexidecimal), B - 66 (42 hex), send 6566 (4142 hex).
The characters permitted are space ' ' (32 base 10, 20
hex) through '}' 125 base 10, 7D hex).
1
16 bit
Integer
RW
Y
86
56
Sensor Abbreviated Name
ASCII bytes 2 and 3
1
16 bit
Integer
RW
Y
87
57