XRGI® 20 COMMISSIONING INSTRUCTION
VERSION 1.0 2019
Check the direction of engine rotation in the Power Unit.
■
The crankshaft rotates to the right
(front view of the Power Unit)
– clockwise
OK
The direction of rotation is correct and you can continue with
Desired produc-
tion.
■
The crankshaft rotates to the left
(front view of the Power Unit)
– counter-clockwise
phases are reversed.
The direction of rotation is incorrect and you need to turn off the generator again;
while the cursor is on
Generator
, press
OK
on the user interface to stop the
generator.
■
Swap two phases in the iQ-Control Panel and recheck the direction of rotation of
the generator; while the cursor is on
Generator
, press
OK
on the user interface
to start the generator.
D E S I R E D P R O D U C T I O N
■
Go to the next page by using the
▲▼
buttons.
■
Move the cursor to
Desired production
by using the
▲▼
buttons and press
OK
on the user interface to activate the field.
■
Change the value to
15.0 kW
by using the
▲▼
buttons. Press
ESC
to save the
entry.
■
Allow the XRGI® system to warm up for approximately 20 to 30 minutes.
■
Then, adjust the value under
Desired production
to
20.0 kW
.
■
Use the
▲▼
buttons to move to the page
Heat Status
.
■
Monitor the operating temperatures of the XRGI® system.
PRODUCTION
1/3
Current production:
Total:
Generator:
Desired production:
Fuel step
Power step:
0.0 kW
3 Wh
0
0
On
0.0 kW
0
Injector:
TMV
TVL
TMK
TLK
TRETURN
83.8 C
78.0 C
68.9 C
91.8 C
84.1 C
o92.00 C
0.92 l/s
32.4 kW
4.1 kW/K
69.9 C
38.1 C
o70.0 C
HEAT STATUS
3/3
87.7 C
87 %
60.7 C
s70.0 C
39.1 C
83.9 C
PRODUCTION
2/3
> NOx
Lambda adjustment:
Lambda adjustment:
Ignition angle:
RPM:
MAP:
ADJUST.
ADJUST.
397 mbar
1048
14.0º
> 737 mV >
-10
> CO
6.2.7
F L U E G A S M E A S U R E M E N T
■
Operate the flue gas analyser in line with the manufacturer’s instructions and
measure the flue gas emission.
■
If the flue gas emissions are outside the required range, adjust the settings under
Lambda adjustment
.
■
If the emissions values are too high/low press:
>NO
X
ADJUST = Lambda adjustment increase by +1
<CO ADJUST = Lambda adjustment decrease by -1
Use the following table to regulate emission levels.
TA B L E F O R T H E R E G U L AT I O N O F E M I S S I O N VA L U E S
XRGI® 20
NO
X
max. 60 ppm
CO
max. 50 ppm
When reducing CO and/or NO
X
values, it takes a couple of minutes before
the change stabilises on your flue gas analyser.
Make small adjustments at a time in order to achieve the correct values.
Summary of Contents for XRGI 6
Page 1: ...VERSION 1 0 2019 01DOC1075 01 COMMISSIONING INSTRUCTION...
Page 2: ......
Page 14: ...XRGI COMMISSIONING INSTRUCTION VERSION 1 0 2019 12...
Page 47: ...XRGI COMMISSIONING INSTRUCTION VERSION 1 0 2019 45 N OT E S...
Page 48: ...XRGI COMMISSIONING INSTRUCTION VERSION 1 0 2019 46 N OT I Z E N...
Page 49: ......
Page 50: ...01DOC1075 01 09 2019 CO M M I S S I O N I N G I N S T R U C T I O N...