Product Description
1.1.
Product introduction
ECAN-E01S is a high-performance industrial-grade Ethernet and CAN-bus data conversion device developed
by Ebyte. It integrates 2 CAN-bus interfaces, 1 EtherNet interface, supports TCP/UDP protocol, and can easily
Complete the intercommunication between CAN-bus network and Ethernet network.
ECAN-E01S has a built-in 120 ohm resistor, which can be enabled by dialing a code; it supports working in
the temperature range of -40°C to 85°C. It has one 10M Ethernet interface; the maximum baud rate of 2 CAN ports
communication is 1Mbps, with TCP Server, TCP Client, UDP and other working modes, and software
configuration parameters can be configured through the host computer. .
1.2.
Features
Integrate 2 CAN-bus interfaces and use plug-in terminal wiring mode;
Support CAN2.0A and CAN2.0B frame format, in line with ISO/DIS 11898 specification;
The baud rate of CAN-bus communication can be freely programmable between 5Kbps~1Mbps;
Dual-channel CAN transceiver, support dual-channel server, maximum support 14-channel connection
Maximum sending data flow: 8000 frames/second; maximum receiving data flow: 14000 frames/second
The time stamp accuracy of the received message at the CAN end can reach 1us;
Support registration package, heartbeat package, short connection function
Support DHCP, DNS;
Support disconnection restart/timeout restart;
Support clear cache function;
Support host computer configuration;
Contains 120 ohm resistance;
Built-in watchdog;
Ethernet port upgrade function;
Operating temperature range: -40
℃
~+85
℃
.