ELF/D Analog Output Connections

The ELF/D provides analog outputs corresponding to airflow or equivalent velocity pressure and temperature.  Analog
outputs available from the ELF/D00 and /D03 versions are 0-10/2-10 VDC; or 0-5/1-5 VDC from the /D01 and /D04
versions.  The /D02 version provides an equivalent Staefa output.  Outputs are capable of driving 20mA loads.  The
analog outputs are not isolated from the input power.  The 24VAC input ground is shared with the analog signal ground
(black wire - GND).  If isolated outputs are desired, the ELF must be powered by a dedicated isolation transformer.

Connect the analog airflow output (white wire), temperature output (green wire) and the signal common (black wire) to
the BAS monitor/control interface using shielded twisted pair cable as shown in Figure 5.  

Converting the ELF/D Analog Output from 2-10VDC or 1-5VDC to an equivalent 4-20mA output 
(Not for Staefa output model with /D02 suffix)

Analog output voltage can be converted to equivalent analog output current by setting the ELF analog output switch
SW2 to 2-10VDC for the ELF/D00 and /D03 versions (or 1-5VDC for the /D01 and /D04 versions), and placing the
proper value of resistor R1 across the ELF analog output signal lines at the BAS control interface as shown in Figure 5.  
For example, on an ELF/D00 (0-10VDC), set SW2 set for 2-10VDC (ON), and use an R1 value of 500 ohms at the BAS
control input interface to produce a corresponding control signal of 4-20mA.  Similarly, for an ELF-xxxx/D01 or /D04
version (0-5VDC), set SW2 for 1-5VDC output, and R1 value of 250 ohms to produce a 4-20 mA control signal.

Figure 5. ELF/D Power and Signal Wiring Interconnections

TEM

P   

 FLO

W

   

   G

ND   

   24

V

JUNCTION BOX

EBTRON ELF

24 VAC POWER INPUT
(SEE NOTE *1)

24 VAC COM / SIGNAL COM

ANALOG AIRFLOW OUT

RED

BLACK

WHITE

24 VAC

TRANSFORMER

(SEE NOTE *1)

RED

BL

AC

K

WHIT

E

4-CONDUCTOR

SHIELDED CABLE (3 FEET)

INCLUDED WITH ELF

(SEE NOTE *2)

*

NOTES:

*1: THE 24 VAC COMMON AND ELF ANALOG OUTPUT SIGNAL COMMON ARE SHARED.  

THEREFORE, ON MULTIPLE ELF INSTALLATIONS ENSURE THAT ALL TRANSMITTERS ARE 
WIRED TO THE SAME TERMINALS ON THE 24 VAC POWER SOURCE.

*2: CONNECT CABLE DRAINS TO EARTH GROUND AT ONE END OF EACH CABLE ONLY.

*3: FOR ELF STANDARD AND MODELS WITH /D01, /D03 and /D04 SUFFIX (NOT FOR /D02) UNIVERSAL INPUT 

CONTROLLER APPLICATIONS WITH PULL-UP RESISTORS, RESISTOR R1 MUST BE CONNECTED ACROSS THE 

CONTROLLER’S ANALOG INPUTS AS SHOWN.  SELECT R1 VALUE AS FOLLOWS:

FOR STANDARD ELF AND /D03 VERSIONS, SET SW2 ON (FOR 2-10VDC OUTPUT), AND SELECT R1=500 OHMS.

FOR ELF /D01 AND /D04 VERSIONS, SET SW2 ON (FOR 1-5VDC OUTPUT) AND SELECT R1=250 OHMS.

*

2

*

2

*

2

*

1

ANALOG TEMPERATURE OUT

GREEN

GREEN

(BLACK)

(WHITE) 
OR 
(GREEN)

+10 VDC

25 K-OHM

200 K-OHM

R1
(SEE NOTE *3)
¼ W MIN

TYPICAL

“UNIVERSAL INPUT “ 

CONTROLLER CIRCUIT

ALTERNATE WIRING FOR

UNIVERSAL INPUT CONTROLLER 

APPLICATION (SEE NOTE *3)

NOT FOR USE WITH ELF MODEL

/D02 WITH STAEFA OUTPUT

SELECT R1 VALUE 

AND CONFIGURE 

SW2 AS DETAILED 

IN NOTE *3.

*

2

TYPICAL

ANALOG INPUT 

BAS

2 CONDUCTOR 

TWISTED PAIR

SHIELDED CABLE

SUPPLIED BY OTHERS

(BLACK) ANALOG COMMON

(WHITE) AIRFLOW OUT

(GREEN) TEMPERATURE OUT

*

2

Summary of Contents for ELF/D Series

Page 1: ...L STAEFA EQUIVALENT OUTPUT FLOW TEMP WITH FLOW INTEGRATION ELF XXXX D03 DUAL 0 10 2 10VDC ANALOG OUTPUT FLOW TEMP AND NO FLOW INTEGRATION ELF XXXX D04 DUAL 0 5 1 5VDC ANALOG OUTPUT FLOW TEMP AND NO FL...

Page 2: ...0 SW1 SW4 CONFIG DIP SWITCH SELECTOR 10 ELF D INITIAL START UP NORMAL OPERATION 11 Converting the Analog Airflow Output Signal from Linear to Volumetric flow FPM to CFM 11 ELF MAINTENANCE 11 ELF STAND...

Page 3: ...output options permits interface to virtually all modern building automation systems BAS EBTRON s proprietary flow loss compensation techniques eliminate inaccuracies typically associated with small d...

Page 4: ...10 2 10VDC 03 5 1 5VDC or Staefa equivalent airflow or equivalent velocity pressure Output Resolution4 0 015 FS D00 and D03 0 03 FS D01 and D04 versions ORDERING GUIDE Specification Notes 1 Accuracy f...

Page 5: ...Placement of the ELF is critical for proper operation and accuracy of the airflow measurement station Figure 2 shows minimum placement requirements for the ELF in typical applications Placement is ind...

Page 6: ...nclosure External duct insulation that interferes with mounting should be temporarily removed prior to installation Mounting requires a 0 875 inches 22 2 mm hole on the insertion side of the duct 1 De...

Page 7: ...ing flow ring Locate ELF 3 inches minimum upstream of box OR 3 inches minimum upstream of flow ring Boxes with no flow rings Locate ELF 3 inches minimum upstream of box EBTRON ELF Actuator by others V...

Page 8: ...power and analog output to customer interface as outlined in the follow ing paragraphs Refer to Figure 5 and the following ELF D cable color code descriptions Red 24 VAC power Black Common ELF Power...

Page 9: ...2 10VDC ON and use an R1 value of 500 ohms at the BAS control input interface to produce a corresponding control signal of 4 20mA Similarly for an ELF xxxx D01 or D04 version 0 5VDC set SW2 for 1 5VD...