Startup_HTA104-P_r1a Page 1 of 2
STARTUP INSTRUCTIONS:
1. Verify that the sensor probes are located where they meet EBTRON published installation guides.
2. Verify that the probes are properly spaced with the airflow arrows pointing in the direction of airflow.
Improperly installed probes will compromise the installed accuracy of the device and degrade system
performance.
3. Verify that the transmitter is installed and wired in accordance with the
HTA104-P Wiring Guide
provided with the transmitter and power is provided to the transmitter.
4. Make sure the ductwork is clean and free of debris prior to fan startup.
5. Move the power switch to the “ON” position. Power-up faults, if detected, are displayed on the LCD.
If any power up faults are detected, resolve all conflicts or contact EBTRON customer service at
1-800-232-8766 before proceeding..
If extension cables have been added, the extension cable length must be entered into the transmitter.
Refer to the Operations and Maintenance Manual for more information.
6. The transmitter is fully functional as a factory calibrated airflow and temperature measurement device
in I-P units (ft, FPM, CFM °F). Airflow (CFM) and temperature (°F) are displayed on the LCD.
If SI units are required, refer to the the Operations and Maintenance Manual.
The factory default airflow output is set to actual airflow (FPM, CFM). If standard (mass) airflow
(SFPM, SCFM) is required, refer to the Operations and Maintenance Manual.
7.
Verify that the area on the hang-tag matches the actual area of the duct or opening where the probes
are located (less any internal insulation). If the area is different, modify the area parameter stored in
the transmitter and use the correct area for any external conversion calculations from FPM to CFM.
Failure to use the correct area will result in volumetric airflow (CFM) measurement error and degrade
system performance. If the area parameter must be changed, refer to the Operations and
Maintenance Manual.
Advantage IV (A4) HTA104-P STARTUP GUIDE
Description
Parameter Default
Optional Settings/Ranges
Units
System of Units
SYS
I-P (US customary)
SI (metric)
Airflow Calculation Method
AIRFLOW
ACT (actual)
STD (standard mass flow)
Altitude (for actual flow correction) ALT
0
0 to 20000 [0 to 6000]
ft [m]
Low Limit Airflow Cutoff
LLIMIT
0 FPM
0 to 500 FPM [0.0 to 2.5 m/s]
Area
AREA
{Order Area}
0.00 to 9999.99 [0.000 to 999.999]
sq ft [sq m]
AO1 Type
AOUT1
4-20mA
0-10V, 0-5 V
AO2 Type
AOUT2
4-20mA
0-10V, 0-5 V
AO1 Assignment
AO1 ASGN
AF (Airflow)
None
AO1 Unit of Measure
AO1 UM
FPM [m/s]
CFM [L/s]
AO1 Minimum Scale Reading
AO1 MS
0
None
FPM [m/s]
AO1 Full Scale Reading
AO1 FS
5000 [25.0]
100 to 15000 [0.5 to 75.0]
FPM [m/s]
AO2 Assignment
AO2 ASGN
TEMP (Temperature) ALRM (Alarm) or TRBL (System Trouble)
AO2 Unit of Measure
AO2 UM
F [C]
None
°F [°C]
AO2 Minimum Scale Reading
AO2 MS
-20 [-30]
-50 to 160 [-50 to 70]
°F [°C]
AO2 Full Scale Reading
AO2 FS
160 [70]
-50 to 160 [-50 to 70]
°F [°C]
HTA104-P Parameters - Factory Defaults and Optional Settings/Ranges
Refer to the O&M Manual for more information and/or additional parameter defaults, settings and ranges.
L2
L1
A1
A2
C
OUT2
OUT1
TYPE C
TYPE B
TYPE A
ACT
C1
C1
C1
C2
C2
C3
C4
mA
VDC